Woodward easYgen-2000 Series User Manual page 131

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Fig. 77: "Extremely inverse" characteristic
ID
Parameter
4030
Monitoring
4034
Inverse time
characteristic
4035
Inverse time
overcurrent
T
=
p
4036
Inverse time
overcurr. I
=
P
4037
Inv time over‐
curr. I
=
start
4031
Alarm class
37535B
Configure Monitoring > Generator > Generator Inverse Time-Ove...
CL
Setting range
Description
[Default]
2
[On]
Overcurrent monitoring is carried out according to the following parameters.
Off
No monitoring is carried out.
2
Selection of the used overcurrent characteristic.
[Normal]
The "normal inverse" tripping curve will be used
High
The "highly inverse" tripping curve will be used
Extreme
The "extremely inverse" tripping curve will be used.
2
0.01 to 1.99 s
Time constant T
[0.06 s]
2
10.0 to 300.0 %
Current constant I
[100.0 %]
2
100.0 to 300.0
Lower tripping value for inverse time-overcurrent protection. If the monitored
%
current is less than I
If I
start
[115.0 %]
2
Class A/B/C/D/
Each limit may be assigned an independent alarm class that specifies what
E/F
action should be taken when the limit is surpassed.
[F]
Notes
For additional information refer to
on page 587
easYgen-2200/2500 | Genset Control
used to calculate the characteristics.
p
used to calculate the characteristics.
P
, the inverse time-overcurrent protection does not trip.
start
is less than I
, I
is used as the lower tripping value.
P
P
Ä Chapter 9.5.1 "Alarm Classes"
Configuration
131