Advertisement

ID
Parameter
5601
Int.voltage
control set‐
point 2
12920
Setp. 2 voltage
5616
Start value
5617
Start delay
5603
Voltage control
setpoint ramp
5604
Voltage control
droop
37535B
Configure Application > Configure Controller > Voltage Control
CL
Setting range
Description
[Default]
05.15
Discrete raise/lower voltage
The setpoint from the discrete raise/lower voltage function is used as setpoint
06.01
Analog input 1
Analog input 1 is used to control the setpoint
06.02
Analog input 2
Analog input 2 is used to control the setpoint
06.03
Analog input 3
Analog input 3 is used to control the setpoint
06.04
Analog input 4
Analog input 4 is used to control the setpoint
Notes
Selecting a different data source may not allow the controller to operate prop‐
erly.
The voltage setpoint may be adjusted within the configured operating limits
Ä Chapter 4.4.1.1 " Generator Operating Voltage / Frequency" on page 107 ).
(
0
50 to 650,000 V
The internal generator voltage setpoint 2 is defined in this screen. This value
is the reference for the voltage controller when performing isolated and/or no-
[400 V]
load operations.
2
Determined by
If this LogicsManager condition is TRUE, the voltage setpoint 2 will be ena‐
LogicsManager
bled, i.e. the setting of parameter overrides the setting of param‐
eter
[(0 & 1) & 1]
Notes
For information on the LogicsManager and its default settings see
Ä Chapter 9.4.1 "LogicsManager Overview" on page 549 .
1
0 to 100 %
The voltage controller is activated when the monitored generator voltage has
exceeded the value configured in this parameter. This prevents the easYgen
[70 %]
from attempting to control the voltage while the engine is completing its start
sequence.
Notes
This value refers to the generator voltage setpoint (parameter
or
5601 Ä p.
1
0 to 999 s
The voltage controller is enabled after the configured time for this parameter
expires.
[5 s]
2
1.00 to 300.00
The different setpoint values are supplied to the controller via this ramp. The
%/s
slope of the ramp is used to alter the rate at which the controller modifies the
setpoint value. The faster the change in the setpoint is to be carried out, the
[5.00 %/s]
greater the value entered here must be.
2
0.0 to 20.0 %
If this control is to be operated on a generator in parallel with other generators
and voltage control is enabled, a droop characteristic curve must be used.
[5.0 %]
Each generator in the system will require the same value to be configured for
the droop characteristic, so that when the system is stable the reactive power
will be distributed proportionally among all generators in relation to their rated
reactive power.
easYgen-2200/2500 | Genset Control
5618 Ä p.
288.
289).
Configuration
5600 Ä p. 288
289