Breakers Mcb - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

ID
Parameter
5708
GCB open time
pulse
4.5.1.9

Breakers MCB

General notes
ID
Parameter
5732
MCB control
(easYgen-2200)
5733
MCB control
(easYgen-2500)
3417
MCB time
pulse
5730
Synchroniza‐
tion MCB
5710
Voltage differ‐
ential MCB
37535B
Configure Application > Configure Breakers > Breakers MCB
CL
Setting range
Description
[Default]
Notes
This parameter only applies to application modes
2
0.10 to 9.90 s
This time defines the length of the GCB open time pulse, if the automatic
switch unblocking GCB is activated.
[1.00 s]
Notes
This parameter only applies to application modes
CL
Setting range
Description
[Default]
2
Off
A MCB is not operated. Relay [R5] (38/39/40) can be freely used.
[1 Relay]
A MCB is operated and if necessary monitored. Relay [R5] (38/39/40) is used
and fixed to this function.
Notes
Even if the MCB operation is switched off and the breaker application mode is
configured to GCB/MCB, the reply of the MCB is observed anyway.
2
Off
A MCB is not operated. Relay [R5] (38/39/40) can be freely used.
1 Relay
A MCB is operated and if necessary monitored. Relay [R5] (38/39/40) is used
and fixed to this function.
[2 Relays]
A MCB is operated and if necessary monitored. Relay [R5] (38/39/40) is used
for the open function, relay [R8] (82/83) to close it. The opening and closing is
carried out with the pulse method.
Notes
Even if the MCB operation is switched off and the breaker application mode is
configured to GCB/MCB, the reply of the MCB is observed anyway.
2
0.10 to 0.50 s
Breaker pulse duration to close the MCB
[0.50 s]
The time of the pulse output may be adjusted to the breaker being utilized.
2
[Slip fre‐
The frequency controller adjusts the frequency in a way, that the frequency of
quency]
the source (busbar) is marginal greater than the target (mains). When the
synchronizing conditions are reached, a close command will be issued. The
slipping frequency is positive to avoid reverse power.
Phase matching
The frequency controller adjusts the phase angle of the source (busbar) to
that of the target (mains), in view of turning the phase difference to zero.
2
0.50 to 20.00 %
The maximum permissible voltage differential for closing the mains circuit
breaker is configured here.
[5.00 %]
easYgen-2200/2500 | Genset Control