Load Share Parameters - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Configuration
Configure Interfaces > Load Share Parameters
ID
Parameter
4843
ECU applica‐
tion
12939
ECU power
mode
4.6.3

Load Share Parameters

ID
Parameter
9923
Load share
Interface
9921
Transfer rate
LS fast mes‐
sage
9920
Load Share
CAN-ID
322
CL
Setting range
Description
[Default]
Notes
The Wodward EGS ECU supports both types of speed deviation control and
may be configured either to "Speed offset" or "Speed setpoint".
In mains parallel operation, the EGS can be configured to receive a real
power setpoint from the easYgen to control the power. In this case, real
power control must be disabled in the easYgen.
This parameter is only visible if ECU remote controlled (param‐
eter
2
[Continuous]
MTU - 3B mode
For details please refer to the manual of your J1939 ECU manufacturer.
Emergency
MTU - 3D mode
For details please refer to the manual of your J1939 ECU manufacturer.
Notes
This parameter is only visible if "Device type" (parameter
configured to "ADEC ECU8 MTU" and "ECU remote controlled" (parameter
15127 Ä p.
2
[Low power
MTU - Low mode
mode]
For details please refer to the manual of your J1939 ECU manufacturer.
High power
MTU - High mode
mode
For details please refer to the manual of your J1939 ECU manufacturer.
Notes
This parameter is only visible if "Device type" (parameter
configured to "ADEC ECU8 MTU" and "ECU remote controlled" (parameter
15127 Ä p.
CL
Setting range
Description
[Default]
2
The interface, which is used for transmitting the load share data is configured
here.
[CAN #1]
Use CAN interface 1.
Off
Deactivate load share interface.
2
0.10 to 0.30 s
The transfer rate defines the time delay between two fast CAN messages.
[0.10 s]
In case of CAN systems with a high bus load (e.g. long distance between the
units with low baud rate), a shorter transfer rate (higher time setting) helps to
reduce the bus load.
2
2xx Hex / 3xx
The first digit of the CAN ID or the range (i.e. 2xx means 200 through 2FF) is
Hex / 4xx Hex /
configured here.
5xx Hex
The last two digits will be assigned by the control with the settings from the
[5xx Hex]
device number (parameter
easYgen-2200/2500 | Genset Control
15127 Ä p.
320) is configured to "On".
320) is configured to "On".
320) is configured to "On".
1702 Ä p.
15102 Ä p.
15102 Ä p.
92).
318) is
318) is
37535B

Advertisement

Table of Contents
loading

Table of Contents