Woodward easYgen-2000 Series User Manual page 594

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Appendix
Event And Alarm Reference > Event History> Alarm Messages
Message text
Meaning
ID
EEPROM failure
The EEPROM checksum is corrupted
1714
The EEPROM check at startup has resulted a defective EEPROM.
GCB fail to close
GCB failed to close
2603
The easYgen has attempted to close the GCB the configured maximum number of attempts and failed.
Depending on the configuration, the easYgen will continue to attempt to close the GCB as long as the con‐
ditions for closing the GCB are fulfilled.
GCB fail to open
GCB failed to open
2604
The easYgen is still receiving the reply "GCB closed" after the GCB open monitoring timer has expired.
GCB syn. timeout
GCB synchronization time exceeded
3064
The easYgen has failed to synchronize the GCB within the configured synchronization time.
Gen act. pwr mismatch
Generator active power mismatch
2924
The deviation between the generator power and the active power setpoint has exceeded the limit for at
least the configured time.
Gen. PF lagging 1
Generator overexcited, limit value 1
2337
The power factor limit 1 has been exceeded at the generator towards inductive (i.e. the current is lagging)
for at least the configured time and does not fall below the value of the hysteresis.
Gen. PF lagging 2
Generator overexcited, limit value 2
2338
The power factor limit 2 has been exceeded at the generator towards inductive (i.e. the current is lagging)
for at least the configured time and does not fall below the value of the hysteresis.
Gen. PF leading 1
Generator underexcited, limit value 1
2387
The power factor limit 1 has fallen below at the generator towards capacitive (i.e. the current is leading) for
at least the configured time and does not exceed the value of the hysteresis.
Gen. PF leading 2
Generator underexcited, limit value 2
2388
The power factor limit 2 has fallen below at the generator towards capacitive (i.e. the current is leading) for
at least the configured time and does not exceed the value of the hysteresis.
Gen. overcurrent 1
Generator overcurrent, limit value 1
2218
The generator current has exceeded the limit value 1 for the generator overcurrent for at least the config‐
ured time and does not fall below the value of the hysteresis.
Gen. overcurrent 2
Generator overcurrent, limit value 2
2219
The generator current has exceeded the limit value 2 for the generator overcurrent for at least the config‐
ured time and does not fall below the value of the hysteresis.
Gen. overcurrent 3
Generator overcurrent, limit value 3
2220
The generator current has exceeded the limit value 3 for the generator overcurrent for at least the config‐
ured time and does not fall below the value of the hysteresis.
Gen. overfrequency 1
Generator overfrequency, limit value 1
1912
The generator frequency has exceeded the limit value 1 for generator overfrequency for at least the config‐
ured time and does not fall below the value of the hysteresis.
Gen. overfrequency 2
Generator overfrequency, limit value 2
1913
The generator frequency has exceeded the limit value 2 for generator overfrequency for at least the config‐
ured time and does not fall below the value of the hysteresis.
Gen. overload IOP 1
Generator overload IOP, limit value 1
2314
The generator power has exceeded the limit value 1 for generator overload in isolated operation (MCB is
open) for at least the configured time and does not fall below the value of the hysteresis.
594
easYgen-2200/2500 | Genset Control
37535B