Configuration
Configure Application > Inputs And Outputs > Analog Inputs
4.5.2.1.2
Analog Inputs 1 to 3
General notes
ID
Parameter
Analog input
{x}: Descrip‐
tion
1025
Input 1
1075
Input 2
1125
Input 3
Analog input
{x}: Type
1000
Input 1
1050
Input 2
1100
Input 3
User defined
min. display
value
(User defined
minimum dis‐
play value)
210
CL
Setting range
Description
[Default]
2
user-defined
The event history will store this text message and it is also displayed on the
visualization screen.
1 to 16 charac‐
ters
If the programmed limit value of the analog input has been reached or
exceeded this text is displayed in the control unit screen.
[Analog inp.
{x}]
Notes
This parameter may only be configured using ToolKit.
2
According to the following parameters different measuring ranges are pos‐
sible at the analog inputs.
[Off]
The analog input is switched off.
VDO 5 bar
The value of the analog input is interpreted with the VDO characteristics 0 to
5 bar.
VDO 10 bar
The value of the analog input is interpreted with the VDO characteristics 0 to
10 bar.
VDO 150 °C
The value of the analog input is interpreted with the VDO characteristics 50 to
150 °C.
VDO 120 °C
The value of the analog input is interpreted with the VDO characteristics 40 to
120 °C.
Pt100
The value of the analog input is interpreted with a Pt100 characteristic.
Linear
Each analog input may be assigned to a linear characteristic curve, which can
be only used for the respective defined input [T{x}] (x = 1 to 2). The minimum
(0 %) and maximum (100 %) value refers to the total measuring range of the
analog input (i.e. 0 to 500 Ohm or 0 to 20 mA) or the values configured as
"Sender value at display min." (parameter
1139 Ä p.
eter
Table A/B
The analog input is assigned to a characteristic curve which is defined over
9 points (stored in a table). Two independent tables (table A and table B) may
be allocated to the analog inputs.
Note that if these tables are to be used with the analog inputs, the defined
points of these tables must be programmed into the control unit.
Notes
For the characteristic curves of the inputs refer to
Inputs Characteristics" on page 486 .
2
-32000 to 32000
The value to be displayed for the minimum of the input range must be entered
here.
[0]
easYgen-2200/2500 | Genset Control
Monitoring of the analog inputs (overrun/underrun)
must be configured manually to the flexible limits
(Ä Chapter 4.4.5 "Flexible Limits" on page 175).
211) and "Sender value at display max." (param‐
1040 Ä p.
211,
1090 Ä p. 211
1039 Ä p.
211,
1089 Ä p. 211
or
1140 Ä p.
211).
Ä Chapter 9.1.2 "VDO
or
37535B