Discrete Inputs - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Characteristic
3.2.10

Discrete Inputs

General notes
37535B
Terminal
A
56
B
57
Fig. 52: MPU - characteristic
Fig. 52 shows the minimal necessary input voltage
depending on frequency.
WARNING!
Hazards due to improper implementation of emer‐
gency stop
Discrete input [DI 01] "Emergency Stop" is only a sig‐
naling input. This input may only be used to signal that
an external emergency stop button has been actuated.
According to EN 60204, this input is not approved to
be used as the emergency stop function.
The emergency stop function must be imple‐
mented external to the control and cannot rely on
the control to function properly.
The discrete inputs are electrically isolated which per‐
mits the polarity of the connections to be either positive
or negative.
All discrete inputs must use the same polarity,
either positive or negative signals, due to the
common ground.
easYgen-2200/2500 | Genset Control
Setup Connections > Discrete Inputs
Description
Amax
MPU input - inductive/
2.5 mm²
switching
MPU input - GND
2.5 mm²
Installation
69