Engine Charge Alternator (D+) - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

ID
Parameter
2660
Monitoring
2663
Delay
2661
Alarm class
2662
Self acknowl‐
edge
4.4.3.11

Engine Charge Alternator (D+)

General notes
37535B
Configure Monitoring > Engine > Engine Charge Alternator (...
CL
Setting range
Description
[Default]
2
[On]
Monitoring of the operating range is carried out according to the following
parameters.
Off
Monitoring is disabled.
2
1 to 999 s
If one of the above mentioned conditions for an operating range failure is ful‐
filled, an alarm will be issued. If the respective condition is not fulfilled any‐
[30 s]
more before the delay time expires, the delay time will be reset.
2
Class A/B/C/D/
Each limit may be assigned an independent alarm class that specifies what
E/F
action should be taken when the limit is surpassed.
[B]
Notes
For additional information refer to
on page 587
2
Yes
The control unit automatically clears the alarm if the fault condition is no
longer detected.
[No]
The control unit does not automatically reset the alarm when the fault condi‐
tion is no longer detected.
The alarm must be acknowledged and reset by manually pressing the appro‐
priate buttons or by activating the LogicsManager output "External acknowl‐
edgement" (via a discrete input or via an interface).
The charge alternator monitoring issues an alarm if the voltage
measured at the auxiliary excitation input D+ (terminal 52) falls
below a fix limit.
The fix limit depends on the power supply voltage. If a power
supply voltage exceeding 16 V is detected, the unit assumes a
24 V system and uses a limit of 20 V. If a power supply voltage
below 16 V is detected, the unit assumes a 12 V system and uses
a limit of 9 V.
easYgen-2200/2500 | Genset Control
If this protective function is triggered, the display indi‐
cates "Operat. range failed" and the logical command
variable "06.31" will be enabled.
Ä Chapter 9.5.1 "Alarm Classes"
If this protective function is triggered, the display indi‐
cates "Charge alt. low volt" and the logical command
variable "05.11" will be enabled.
Configuration
167