4.5.9

Engine

4.5.9.1

Engine Type

ID
Parameter
3321
Start/Stop
mode logic
37535B
Type
Table 53: Analog outputs - signal type selection
CL
Setting range
Description
[Default]
2
Diesel or gas engine start/stop logic must be selected.
[Diesel]
Start sequence
The relay "Preglow" will be energized for the preheating time period ("Pre‐
glow" is displayed). Following preheating, the fuel solenoid is first energized
and then the starter is engaged ("Start" is displayed).
When the configured firing speed is exceeded, the starter is disengaged and
the fuel solenoid remains energized via the firing speed. "Ramp to rated" is
displayed until the engine monitoring delay timer expires and the start
sequence has finished.
If the engine fails to start, a start pause is initiated ("Start - Pause" is dis‐
played). If the number of unsuccessful start attempts reaches the configured
value, an alarm message will be issued ("Start fail" is displayed).
Stop sequence
After opening the GCB, the coasting time starts and the engine runs without
load ("Cool down" is displayed). On termination of the coasting time, the fuel
solenoid is de-energized, and the engine is stopped ("Stop engine" is dis‐
played). If the engine cannot be stopped via the fuel solenoid, the alarm mes‐
sage "Eng. stop malfunct." is displayed.
Start/stop diagram
The formula signs and indices mean:
n
n
n
n
n
n
n
n
Refer to Fig. 88.
easYgen-2200/2500 | Genset Control
Configure Application > Engine > Engine Type
Setting in parameter
External
5229/5243
resistor
20 to 0mA (10 to 0V)
User defined
tPRE Auxiliary services prerun [s] (parameter
tPH Preglow time [s] (parameter
tST Starter time [s] (parameter
tSP Start pause [s] (parameter
tED Engine delayed monitoring [s] (parameter
tPOST Auxiliary services postrun [s] (parameter
tCD Cool down time [s] (parameter
tGS Generator stable time [s] (parameter
Configuration
Range
Lower
level
10 to 0V
10 Vdc
3300 Ä p.
240)
3308 Ä p.
231)
3306 Ä p.
238)
3307 Ä p.
239)
3315 Ä p.
239)
3301 Ä p.
240)
3316 Ä p.
240)
3415 Ä p.
204)
Upper
level
0 Vdc
229