Installation
Setup Connections > Analog Inputs
Wiring single-pole senders
(easYgen-2500 P1 only)
Wiring single and two-pole senders
simultaneously
74
An accuracy of ≤ 2.5 % may be achieved when using single-pole
senders. The specified accuracy of ≤ 2.5 % for single-pole sensors
can only be achieved if the differential voltage between the genset
chassis ground and PE does not exceed +/- 2.5 V.
Fig. 59: Analog inputs - wiring single-pole senders
Terminal
Description
54
Power supply 0 Vdc
53
Power supply 12/24 Vdc (8 to 40.0 Vdc)
10
Analog input [AI 01/02/03] ground
11
Analog input [AI 01]
12
Analog input [AI 02]
13
Analog input [AI 03]
Table 29: Wiring single-pole senders
Terminal
Description
67
Analog input [AI 04] ground, connected to AI ground (ter‐
minal 10)
68
Analog input [AI 04]
Table 30: Wiring single-pole senders (easYgen-2500 P1 only)
An accuracy of ≤ 2.5% may be achieved when using single-pole
senders. It is possible to combine single- and two-pole senders.
The specified accuracy of ≤ 2.5% for single-pole sensors can only
be achieved if the differen-tial voltage between the genset chassis
ground and PE does not exceed +/- 2.5V.
easYgen-2200/2500 | Genset Control
A
max
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
A
max
2.5 mm²
2.5 mm²
37535B