Advertisement

Operation
Front Panel Access > Specialised Menu Screens > Synchroscope (Generator/Bu...
5.2.4.4

Setpoints

Fig. 125: Setpoints screen (MANUAL
operating mode)
Fig. 126: Setpoints screen (AUTO‐
MATIC operating mode)
5.2.4.5

Synchroscope (Generator/Busbar Or Generator/Mains)

Fig. 127: Setpoints screen (AUTO‐
MATIC operating mode)
Fig. 128: Setpoints screen (MANUAL
operating mode)
350
The setpoint is displayed on the left and the actual value is dis‐
played on the right half of the screen.
The source, which is used for setpoint 1 or setpoint 2, is displayed
with the respective LogicsManager function number.
The setpoints may only be adjusted if the respective controller is
enabled. Frequency and voltage may be adjusted within the config‐
ured operating limits.
Active power may be adjusted between 0 and the configured load
control setpoint maximum. The power factor may be adjusted
between 0.71 leading and 0.71 lagging.
Symbol/Softkey
Description
Indicates the generator power (actual value).
Indicates the mains power (actual value).
Raise the selected setpoint.
Lower the selected setpoint.
The square symbol indicates the actual phase angle between gen‐
erator and busbar or generator and mains (depending on configu‐
ration). A complete left position of the square symbol means -180°
and complete right position means +180°.
The frequency and voltage differences are indicated in the center
of the circle.
Symbol/Softkey
Description
Indicates the actual phase angle between generator and
busbar or generator and mains.
Operating mode MANUAL: Raise voltage/frequency.
Operating mode MANUAL: Lower voltage/frequency.
easYgen-2200/2500 | Genset Control