Generator Voltage Asymmetry - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Configuration
Configure Monitoring > Generator > Generator Voltage Asymmetry
ID
Parameter
2402
Self acknowl‐
edge
2408
2403
Delayed by
engine speed
2409
4.4.1.11

Generator Voltage Asymmetry

General notes
ID
Parameter
3900
Monitoring
122
CL
Setting range
Description
[Default]
Notes
For additional information refer to
on page 587
2
Yes
The control unit automatically clears the alarm if the fault condition is no
longer detected.
[No]
The control unit does not automatically reset the alarm when the fault condi‐
tion is no longer detected.
The alarm must be acknowledged and reset by manually pressing the appro‐
priate buttons or by activating the LogicsManager output "External acknowl‐
edgement" (via a discrete input or via an interface).
2
Yes
Monitoring for fault conditions is not performed until engine delayed moni‐
toring is enabled. The engine monitoring delay time (param‐
eter
parameters assigned this delay.
[No]
Monitoring for this fault condition is continuously enabled regardless of engine
speed.
The voltage asymmetry alarm monitors the individual three-phase
voltages of the generator. Voltage asymmetry monitoring is always
performed phase-phase (delta). The percentage threshold value is
the permissible variation from the average measured voltage of all
three phases.
If a measured voltage exceeds a configured permissible asymmet‐
rical voltage deviation from the average voltage value, an alarm is
issued.
Refer to
for the triggering characteristic of this monitoring function.
CL
Setting range
Description
[Default]
2
[On]
Voltage asymmetry monitoring is carried out according to the following
parameters.
Off
No monitoring is carried out.
easYgen-2200/2500 | Genset Control
Ä Chapter 9.5.1 "Alarm Classes"
3315 Ä p.
239) must expire prior to fault monitoring being enabled for
If this protective function is triggered, the display indi‐
cates "Gen. volt. asymmetry" and the logical command
variable "06.18" will be enabled.
Ä Chapter 9.1.1 "Triggering Characteristics" on page 481
This monitoring function is only enabled if Generator
voltage measuring (parameter
ured to "3Ph 4W" or "3Ph 3W".
1851 Ä p.
96) is config‐
37535B

Advertisement