Magnetic Pickup Unit (Mpu) - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Installation
Setup Connections > Magnetic Pickup Unit (MPU)
Phasor diagram
Inductive
Diagram
3.2.9

Magnetic Pickup Unit (MPU)

General notes
Overview
Schematic and terminals
68
The phasor diagram is used from the generator's view.
The shield of the MPU (Magnetic Pickup Unit) connec‐
tion cable must be connected to a single point ground
terminal near the easYgen.
The shield must not be connected at the MPU side of
the cable.
The number of teeth on the flywheel reference gear
and the flywheel speed must be configured so that the
magnetic pickup input frequency does not exceed
14kHz.
Fig. 50: MPU - overview
Fig. 51: MPU - input
easYgen-2200/2500 | Genset Control
Capacitive
37535B