Configuration
Configure Measurement > Configure Transformer
ID
Parameter
1812
Busb1 PT sec‐
ondary rated
volt.
(Busbar 1
potential trans‐
former secon‐
dary voltage
rating )
1804
Mains PT pri‐
mary rated
voltage
(Mains potential
transformer pri‐
mary voltage
rating
1803
Mains PT sec‐
ondary rated
volt.
(Mains potential
transformer sec‐
ondary voltage
rating)
100
CL
Setting range
Description
[Default]
2
50 to 480 V
Some applications may require the use of potential transformers to facilitate
measuring the busbar voltages. The rating of the secondary side of the poten‐
[400 V]
tial transformer must be entered into this parameter.
If the application does not require potential transformers (i.e. the measured
voltage is 480 V or less), then the measured voltage will be entered into this
parameter.
n
n
Notes
WARNING: Only connect the measured voltage to either the 120 Vac or the
480 Vac inputs. Do not connect both sets of inputs to the measured system.
The control is equipped with dual voltage measuring inputs. The voltage
range of these measurement inputs is dependent upon input terminals are
used. This value refers to the secondary voltages of the potential trans‐
formers, which are directly connected to the control.
2
50 to 650000 V
Some applications may require the use of potential transformers to facilitate
measuring the voltages to be monitored. The rating of the primary side of the
[400 V]
potential transformer must be entered into this parameter.
Notes
If the application does not require potential transformers (i.e. the measured
voltage is 480 V or less), then the measured voltage will be entered into this
parameter.
2
50 to 480 V
Some applications may require the use of potential transformers to facilitate
measuring the mains voltages. The rating of the secondary side of the poten‐
[400 V]
tial transformer must be entered into this parameter.
If the application does not require potential transformers (i.e. the measured
voltage is 480 V or less), then the measured voltage will be entered into this
parameter.
n
n
Notes
WARNING: Only connect the measured voltage to either the 120 Vac or the
480 Vac inputs. Do not connect both sets of inputs to the measured system.
The control is equipped with dual voltage measuring inputs. The voltage
range of these measurement inputs is dependent upon input terminals are
used. This value refers to the secondary voltages of the potential trans‐
formers, which are directly connected to the control.
easYgen-2200/2500 | Genset Control
Rated voltage: 120 Vac (this parameter configured between 50 and
130 V)
Busbar voltage: Terminals 22/24/26/28
Rated voltage: 480 Vac (this parameter configured between 131 and
480 V)
Busbar voltage: Terminals 23/25/27/29
Rated voltage: 120 Vac (this parameter configured between 50 and
130 V)
Mains voltage: Terminals 22/24/26/28
Rated voltage: 480 Vac (this parameter configured between 131 and
480 V)
Mains Voltage: Terminals 23/25/27/29
37535B