J1939 Interface - Red Stop Alarm - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

ID
Parameter
15110
Monitoring
15114
Delay
15111
Alarm class
15112
Self acknowl‐
edge
15113
Delayed by
engine speed
4.4.6.6

J1939 Interface - Red Stop Alarm

General notes
ID
Parameter
15115
Monitoring
37535B
Configure Monitoring > Miscellaneous > J1939 Interface - Red Stop...
CL
Setting range
Description
[Default]
2
On
Monitoring of the J1939 interface is carried out according to the following
parameters.
[Off]
Monitoring is disabled.
2
2 to 6500 s
The delay is configured with this parameter. If the interface does not receive a
CAN SAE J1939 protocol message before the delay expires, the action speci‐
[10 s]
fied by the alarm class is initiated.
The delay timer is re-initialized after every message is received.
2
Class A/B/C/D/
Each limit may be assigned an independent alarm class that specifies what
E/F/Control
action should be taken when the limit is surpassed.
[B]
Notes
For additional information refer to
on page 587
2
[Yes]
The control unit automatically clears the alarm if the fault condition is no
longer detected.
No
The control unit does not automatically reset the alarm when the fault condi‐
tion is no longer detected.
The alarm must be acknowledged and reset by manually pressing the appro‐
priate buttons or by activating the LogicsManager output "External acknowl‐
edgement" (via a discrete input or via an interface).
2
Yes
Monitoring for fault conditions is not performed until engine delayed moni‐
toring is enabled. The engine monitoring delay time (param‐
eter
parameters assigned this delay.
[No]
Monitoring for this fault condition is continuously enabled regardless of engine
speed.
This watchdogs monitors, whether a specific alarm bit is received
from the CAN J1939 interface. This enables to configure the
easYgen in a way that a reaction is caused by this bit (e.g.
warning, shutdown).
CL
Setting range
Description
[Default]
2
On
Monitoring of the Red Stop Lamp message from the ECU is carried out
according to the following parameters.
[Off]
Monitoring is disabled.
easYgen-2200/2500 | Genset Control
Ä Chapter 9.5.1 "Alarm Classes"
3315 Ä p.
239) must expire prior to fault monitoring being enabled for
If this protective function is triggered, the display indi‐
cates "Red stop lamp" and the logical command vari‐
able "05.13" will be enabled.
Configuration
183