Appendix
LogicsManager Reference > Factory Settings
9.4.5

Factory Settings

Functions
Simple (function)
[00.0x] Flag {x}; {x} = 1 to 7
If TRUE, flag {x} becomes TRUE.
Deactivated by default.
[00.08] Flag 8 - pre-configured to engine start via timer
If TRUE, flag 8 becomes TRUE.
TRUE once the configured time 1 has been
reached [11.01], and the configured time 2
[11.02] has not been reached as well if the cur‐
rent day is the configured day [11.03]
Ä Chapter 4.7 "Configure LogicsManager"
(
on page 323 )
Not available in operating modes "STOP" and
"MAN"
[00.09] Start request in Auto
If TRUE, the engine is started in AUTOMATIC
operating mode.
TRUE once discrete input [DI 02] is energized.
Note: This function is pre-configured and may be
activated by passing through the command vari‐
ables [00.08] LM: Flag 8 or [04.03] Remote
request ('―' instead of '0').
Not available in operating modes "STOP" and
"MAN".
[00.10] Stop request in Auto
If TRUE, the engine is either stopped in AUTO‐
MATIC operating mode or a start of the engine is
suppressed (also an emergency operation).
Deactivated by default.
Not available in operating modes "STOP" and
"MAN".
[00.11] Inhibit emergency run
If TRUE, an emergency operation is inhibited or
interrupted.
Deactivated by default.
Not available in operating modes "STOP" and
"MAN". Only available in application mode
578
Extended (configuration)
.
easYgen-2200/2500 | Genset Control
Result
FALSE
dependent on
timer
dependent on
[DI 02]
FALSE
FALSE