Woodward easYgen-2000 Series User Manual page 214

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Configuration
Configure Application > Inputs And Outputs > Analog Inputs
ID
Parameter
Filter time con‐
stant
10113
Input 1
10114
Input 2
10116
Input 3
Bargraph min‐
imum
3632
Input 1
3634
Input 2
3636
Input 3
Bargraph max‐
imum
3633
Input 1
3635
Input 2
3637
Input 3
Value format
214
CL
Setting range
Description
[Default]
2
A filter time constant may be used to reduce the fluctuation of an analog input
reading. This filter time constant assesses the average of the signal according
to the following formula:
n
Off
The analog input is displayed without filtering.
1
Cut-off-frequency = 7.96 Hz (filter time constant = 0.02 s)
2
Cut-off-frequency = 3.98 Hz (filter time constant = 0.04 s)
[3]
Cut-off-frequency = 1.99 Hz (filter time constant = 0.08 s)
4
Cut-off-frequency = 0.99 Hz (filter time constant = 0.16 s)
5
Cut-off-frequency = 0.50 Hz (filter time constant = 0.32 s)
-32000 to 32000
The start value for the bar graph display of the analog input is defined here.
The value must be entered according to the display format, which refers to
[0]
the analog input type (parameter
2
Notes
This parameter is only effective if parameter
"Linear" or "Table A/B".
-32000 to 32000
The end value for the bar graph display of the analog input is defined here.
The value must be entered according to the display format, which refers to
[1000]
the analog input type (parameter
2
Notes
This parameter is only effective if parameter
"Linear" or "Table A/B".
2
1 to 8 character
To display the measuring value of the analog input for the analog input types
text
linear as well as Table A and Table B (parameter
this parameter is to be used to define the format.
[000000]
The zeros in the numeric display are used for the measuring values and are
configurable. The placeholders for the digits may have symbols (i.e.
commas).
easYgen-2200/2500 | Genset Control
Cut-off-frequency =
1 / (20 ms * 2 * π * 2
N - 1
)
whereby "N" is this parameter.
1000 Ä p.
1000 Ä p.
210).
1000 Ä p. 210
is configured to
210).
1000 Ä p. 210
is configured to
1000 Ä p.
210) correctly
37535B