Configuration
Configure Monitoring > Generator > Generator Phase Rotation
ID
Parameter
3950
Monitoring
3954
Generator
phase rotation
3951
Alarm class
3952
Self acknowl‐
edge
3953
Delayed by
engine speed
128
CL
Setting range
Description
[Default]
2
[On]
Phase rotation monitoring is carried out according to the following parame‐
ters.
Off
No monitoring is carried out.
2
[CW]
The three-phase measured generator voltage is rotating CW (clock-wise; that
means the voltage rotates in L1-L2-L3 direction; standard setting).
CCW
The three-phase measured generator voltage is rotating CCW (counter clock-
wise; that means the voltage rotates in L1-L3-L2 direction).
2
Class A/B/C/D/
Each limit may be assigned an independent alarm class that specifies what
E/F
action should be taken when the limit is surpassed.
[F]
Notes
For additional information refer to
on page 587
2
Yes
The control unit automatically clears the alarm if the fault condition is no
longer detected.
[No]
The control unit does not automatically reset the alarm when the fault condi‐
tion is no longer detected.
The alarm must be acknowledged and reset by manually pressing the appro‐
priate buttons or by activating the LogicsManager output "External acknowl‐
edgement" (via a discrete input or via an interface).
2
[Yes]
Monitoring for fault conditions is not performed until engine delayed moni‐
toring is enabled. The engine monitoring delay time (param‐
eter
parameters assigned this delay.
No
Monitoring for this fault condition is continuously enabled regardless of engine
speed.
easYgen-2200/2500 | Genset Control
The direction of configured rotation being monitored by
the control unit is displayed on the screen.
If this protective function is triggered, the display indi‐
cates "Gen.ph.rot. mismatch" and the logical command
variable "06.21" will be enabled.
This monitoring function is only enabled if Generator
voltage measuring (parameter
ured to "3Ph 4W" or "3Ph 3W" and the measured
voltage exceeds 50 % of the rated voltage (param‐
eter
1766 Ä p.
95) or if Generator voltage measuring
(parameter
1851 Ä p.
(in this case, the phase rotation is not evaluated, but
defined by the 1Ph2W phase rotation (param‐
eter
1859 Ä p.
96)).
Ä Chapter 9.5.1 "Alarm Classes"
3315 Ä p.
239) must expire prior to fault monitoring being enabled for
1851 Ä p.
96) is config‐
96) is configured to "1Ph 2W"
37535B