Engine/Mains Active Power Mismatch

General notes
ID
Parameter
2930
Monitoring
2935
Limit
2933
Delay
2931
Alarm class
162
CL
Setting range
Description
[Default]
2
Yes
The control unit automatically clears the alarm if the fault condition is no
longer detected.
[No]
The control unit does not automatically reset the alarm when the fault condi‐
tion is no longer detected.
The alarm must be acknowledged and reset by manually pressing the appro‐
priate buttons or by activating the LogicsManager output "External acknowl‐
edgement" (via a discrete input or via an interface).
If enabled, this monitoring function becomes only active if gener‐
ator power control is enabled and the active power setpoint is con‐
figured to "Import" or "Export" (refer to
Control" on page 276 ). If the measured import or export power
deviates from the power setpoint by a value exceeding the limit
configured in parameter
delay configured in parameter
issued.
CL
Setting range
Description
[Default]
2
[On]
On Monitoring of the mains active power mismatch is carried out according to
the following parameters.
Off
Monitoring is disabled.
2
1.0 to 99.9 %
If the difference between the measured import or export power and the power
setpoint exceeds this value for at least the delay time (param‐
[5.0 %]
eter
class is initiated.
Notes
This value refers to the mains rated active power (parameter
2
3 to 65000 s
If the monitored active power mismatch exceeds the threshold value config‐
ured in parameter
[30 s]
will be issued.
Notes
If the monitored active power mismatch falls below the threshold (minus the
hysteresis) before the delay expires the time will be reset.
2
Class A/B/C/D/
Each limit may be assigned an independent alarm class that specifies what
E/F
action should be taken when the limit is surpassed.
[B]
easYgen-2200/2500 | Genset Control
2935 Ä p. 162
2933 Ä p.
If this protective function is triggered, the display indi‐
cates "Mns act.pwr mismatch" and the logical com‐
mand variable "07.16" will be enabled.
2933 Ä p.
162) without interruption, the action specified by the alarm
2935 Ä p. 162
for the delay time configured here, an alarm
Ä Chapter 4.5.12.2 "Load
for a time exceeding the
162, an alarm will be
1748 Ä p.
95).