Configuration
Configure Application > Configure Controller > Frequency Control
ID
Parameter
5500
Int. freq. con‐
trol setpoint 1
(Internal fre‐
quency control
setpoint 1)
5519
Frequency set‐
point 2 source
274
CL
Setting range
Description
[Default]
06.03
Analog input 3
Analog input 3 is used to control the setpoint
Notes
Selecting a different data source may cause the controller to not operate
properly.
The frequency setpoint may be adjusted within the configured operating limits
(
Ä Chapter 4.4.1.1 " Generator Operating Voltage / Frequency" on page 107 ).
0
15.00 to 85.00
The internal generator frequency setpoint 1 is defined in this screen.
Hz
This value is the reference for the frequency controller when performing iso‐
[50.00 Hz]
lated and/or no-load operations.
Generally 50 Hz or 60 Hz will be the values entered into this parameter. It is
possible to enter a different value here.
2
Determined by
The Frequency setpoint 2 source may be selected from the available data
AnalogManager
sources.
Though it is possible to select from all available data sources
(
Ä Chapter 9.3.1 "Data Sources" on page 533 ), only the following data
sources may be used:
05.01
Internal frequency setpoint 1
Internal frequency control setpoint 1 (parameter
setpoint 2
[05.02]
Internal frequency setpoint 2
Internal frequency control setpoint 2 (parameter
setpoint 2
05.03
Interface frequency setpoint
The setpoint, which is transmitted via the interface, is used as setpoint
05.13
Discrete raise/lower frequency
The setpoint from the discrete raise/lower frequency function is used as set‐
point
06.01
Analog input 1
Analog input 1 is used to control the setpoint
06.02
Analog input 2
Analog input 2 is used to control the setpoint
06.03
Analog input 3
Analog input 3 is used to control the setpoint
Notes
Selecting a different data source may cause the controller to not operate
properly.
The frequency setpoint may be adjusted within the configured operating limits
Ä Chapter 4.4.1.1 " Generator Operating Voltage / Frequency" on page 107 ).
(
easYgen-2200/2500 | Genset Control
5500 Ä p.
274) is used as
5501 Ä p.
275) is used as