Generator Leading Power Factor (Level 1 & 2) - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

ID
Parameter
2329
Limit
2335
2330
Delay
2336
2326
Alarm class
2332
2327
Self acknowl‐
edge
2333
2328
Delayed by
engine speed
2334
4.4.1.16
Generator Leading Power Factor (Level 1 & 2)
General notes
37535B
Configure Monitoring > Generator > Generator Leading Power Fa...
CL
Setting range
Description
[Default]
2
-0.999 to 1.000
The values that are to be monitored for each threshold limit are defined here.
2329 [+ 0.900]
2335: [+ 0.700]
Notes
If the power factor becomes more lagging (i.e. inductive, Fig. 78) than a lag‐
ging PF value (positive) or a leading PF value (negative) for at least the delay
time (parameters
action specified by the alarm class is initiated.
2
0.02 to 99.99 s
If the monitored generator power factor is more lagging than the configured
limit for the delay time configured here, an alarm will be issued.
2330: [30.00 s]
2336: [1.00 s]
Notes
If the monitored generator power factor returns within the limit before the
delay expires the time will be reset.
2
Class A/B/C/D/
Each limit may be assigned an independent alarm class that specifies what
E/F
action should be taken when the limit is surpassed.
2326: [B]
2332: [E]
Notes
For additional information refer to
on page 587
2
Yes
The control unit automatically clears the alarm if the fault condition is no
longer detected.
[No]
The control unit does not automatically reset the alarm when the fault condi‐
tion is no longer detected.
The alarm must be acknowledged and reset by manually pressing the appro‐
priate buttons or by activating the LogicsManager output "External acknowl‐
edgement" (via a discrete input or via an interface).
2
[Yes]
Monitoring for fault conditions is not performed until engine delayed moni‐
toring is enabled. The engine monitoring delay time (param‐
eter
parameters assigned this delay.
No
Monitoring for this fault condition is continuously enabled regardless of engine
speed.
The power factor is monitored for becoming more leading (i.e.
capacitive) than an adjustable limit. This limit may be a leading or
lagging power factor limit. There are two leading power factor
alarm levels available in the control. This monitoring function may
be used for monitoring an underexcitation with a warning and a
shutdown alarm level. Both alarms are definite time alarms.
Refer to
on page 372 for a detailed description of this monitoring function.
easYgen-2200/2500 | Genset Control
2330 Ä p. 133
or
Ä Chapter 9.5.1 "Alarm Classes"
3315 Ä p.
239) must expire prior to fault monitoring being enabled for
Ä Chapter 6.4.1 "Generator Excitation Protection"
Configuration
2336 Ä p.
133) without interruption, the
133

Advertisement

Table of Contents
loading

Table of Contents