Configuration
Configure Monitoring > Miscellaneous > Multi-Unit Parameter Alig...
188
If at least one of these parameters is configured dif‐
ferent in at least one of the units, the display indicates
"Parameter alignment" on all units and the logical com‐
mand variable "08.16" will be enabled.
This alarm is always self-acknowledging, i.e. the control automati‐
cally clears the alarm if it is no longer valid.
The setting of the following parameters will be monitored:
Parameter
Start stop mode
Fit size of engine
Fit service hours
Changes of engines
IOP Reserve power
IOP Hysteresis
IOP Max. generator load
IOP Min. generator load
IOP Dynamic
IOP Add on delay
IOP Add on delay at rated load
IOP Add off delay
MOP Minimum load
MOP Reserve power
MOP Hysteresis
MOP Max. generator load
MOP Min. generator load
MOP Dynamic
1
MOP Add on delay
MOP Add on delay at rated load
MOP Add off delay
Transfer rate LS fast message
Table 45: Multi-unit parameter alignment - monitored parameters
1
This parameter is not visible and therefore not config‐
urable in the easYgen-2000 Series. Nevertheless, this
parameter plays a role if there is load share between
easYgen-2000 and easYgen-3000 devices. Please
make sure, to configure this parameter to the default
value in the easYgen-3000 Series to avoid an error
message.
easYgen-2200/2500 | Genset Control
1
1
1
1
ID
5752 Ä p. 252
5754 Ä p. 253
5755 Ä p. 253
5756 Ä p. 254
5760 Ä p. 256
5761 Ä p. 256
5762 Ä p. 256
5763 Ä p. 256
5757 Ä p. 257
5764 Ä p. 259
5765 Ä p. 259
5766 Ä p. 259
5767 Ä p. 259
5768
5769 Ä p. 260
5770
5771
5758
5772 Ä p. 262
5773
5774 Ä p. 262
9921 Ä p. 322
37535B