Woodward easYgen-2000 Series User Manual page 444

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Application
Modbus Applications > Changing Parameter Settings > Configuration Of LogicsMan...
Word 0
Word 1
low
high
low
high
byt
byte
byt
byte
e
e
2C01 (hex)
E803 (hex)
6.6.2.4.5
Configuration Of LogicsManager Function "External Acknowledge"
Example
444
Word 2
"as is"
1232 (hex)
Fig. 229: Modscan32 at address 12121
Copy the complete message of 7 words to address 12121 ff
(12120+1) in one step.
This is shown in (Fig. 229) using the ModScan32 software.
The "Ext. acknowledge" LogicsManager function (parameter
12490 Ä p.
acknowledgement is performed as soon as the remote acknowl‐
edge signal is enabled.
Refer to the
Acknowledgement" on page 376 for information on configuration
via HMI or ToolKit.
External acknowledge may be enabled by setting bit 4 (external
acknowledge) of the remote control word 503 to HIGH (refer to
Ä Chapter 9.2.3 "Additional Data Identifier" on page 527 ).
Fig. 230: LogicsManager function sample 12490
easYgen-2200/2500 | Genset Control
Word 3
"as is"
1000 (hex)
180) can be configured in a way that an external
Ä Chapter 6.4.4 "Performing Remote Start/Stop And
Word 4
Word 5
Word 6
low
high
low
high
low
byt
byte
byt
byte
byt
e
e
e
0802 (hex)
0700 (hex)
FB00 (hex)
high
byte
37535B

Advertisement

Table of Contents
loading

Table of Contents