Engine Start Failure; Engine Shutdown Malfunction - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Configuration
Configure Monitoring > Engine > Engine Shutdown Malfunctio...
ID
Parameter
3122
Self acknowl‐
edge
4.4.3.7

Engine Start Failure

General notes
ID
Parameter
3303
Monitoring
3304
Alarm class
3305
Self acknowl‐
edge
4.4.3.8

Engine Shutdown Malfunction

General notes
164
CL
Setting range
Description
[Default]
2
Yes
The control unit automatically clears the alarm if the fault condition is no
longer detected.
[No]
The control unit does not automatically reset the alarm when the fault condi‐
tion is no longer detected.
The alarm must be acknowledged and reset by manually pressing the appro‐
priate buttons or by activating the LogicsManager output "External acknowl‐
edgement" (via a discrete input or via an interface).
If it is not possible to start the engine within a configured number of
start attempts (refer to
on page 236 ), an alarm will be initiated.
CL
Setting range
Description
[Default]
2
[On]
Monitoring of the start sequence is carried out according to the following
parameters.
Off
Monitoring is disabled.
2
Class A/B/C/D/
Each limit may be assigned an independent alarm class that specifies what
E/F
action should be taken when the limit is surpassed.
[F]
Notes
For additional information refer to
on page 587
2
Yes
The control unit automatically clears the alarm if the fault condition is no
longer detected.
[No]
The control unit does not automatically reset the alarm when the fault condi‐
tion is no longer detected.
The alarm must be acknowledged and reset by manually pressing the appro‐
priate buttons or by activating the LogicsManager output "External acknowl‐
edgement" (via a discrete input or via an interface).
If it is not possible to stop the engine within a configured time, an
alarm will be initiated.
easYgen-2200/2500 | Genset Control
Ä Chapter 4.5.9.2 "Engine Start/Stop"
If this protective function is triggered, the display indi‐
cates "Start fail" and the logical command variable
"05.08" will be enabled.
Ä Chapter 9.5.1 "Alarm Classes"
37535B