Woodward easYgen-2000 Series User Manual page 303

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Example
Fig. 102: Load sharing - grouping
ID
Parameter
1723
Segment
number
12929
Segment no.2
act
12928
Segment no.3
act
12927
Segment no. 4
act
5568
Mode ext. load
share gateway
37535B
Configure Application > Configure Controller > Load Share Control
Six gensets (G1 through G6) supply a system with two group
breakers (A, B) as shown in . All gensets have the same segment
number configured #1 (parameter
Case
I
Case
II
Case
III
CL
Setting range
Description
[Default]
2
1 to 32
The genset is assigned a load share segment number with this parameter.
This segment number may be overridden by the following parameters
[1]
12929 Ä p.
2
Determined by
Once the conditions of the LogicsManager have been fulfilled, this genset is
LogicsManager
assigned load share segment number 2 (this parameter has priority over
parameters
[(0 & 1) & 1]
Notes
For information on the LogicsManager and its default settings see
Ä Chapter 9.4.1 "LogicsManager Overview" on page 549 .
2
Determined by
Once the conditions of the LogicsManager have been fulfilled, this genset is
LogicsManager
assigned load share segment number 3 (this parameter has priority over
parameters
[(0 & 1) & 1]
Notes
For information on the LogicsManager and its default settings see
Ä Chapter 9.4.1 "LogicsManager Overview" on page 549 .
2
Determined by
Once the conditions of the LogicsManager have been fulfilled, this genset is
LogicsManager
assigned load share segment number 4.
[(0 & 1) & 1]
Notes
For information on the LogicsManager and its default settings see
Ä Chapter 9.4.1 "LogicsManager Overview" on page 549 .
2
The operation mode for the external Woodward Load Share Gateway (LSG)
is configured here.
easYgen-2200/2500 | Genset Control
- Group breakers A and B are closed and G1 through
G6 supply the same busbar. The same segment
number is configured to each genset since all gen‐
sets supply the same busbar.
- Group breaker A is closed and group breaker B is
open (G1 through G4 supply a different busbar than
G5 and G6). A different segment number must be
selected for G5 and G6 by enabling the LogicsMan‐
ager function "Segment no.2 act" (param‐
eter
12929 Ä p.
303) in order to change the seg‐
ment number of G5 and G6 to #2.
- Group breakers A and B are open (G1 and G2, G3
and G4, as well as G5 and G6 supply different bus‐
bars).
A different segment number must be selected for G3
and G4 (LogicsManager function "Segment no.2 act"
(parameter
12929 Ä p.
G6 (LogicsManager function "Segment no.3 act"
(parameter
12928 Ä p.
With this, the segment number of G3 and G4 is
changed to #2 and the segment number of G5 and
G6 is changed to #3.
303,
12928 Ä p.
303, and
12928 Ä p. 303
and
12927 Ä p.
12927 Ä p.
303).
Configuration
1723 Ä p.
303)
303)) as well as to G5 and
303)).
12927 Ä p.
303.
303).
303