9.2.3

Additional Data Identifier

9.2.3.1

Transmit Data

Remote control word 1
Parameter
Object ID
Name
no.
503
21F7h
Control word 1
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Table 99: Remote control telegram
37535B
Data Protocols > Additional Data Identifier > Transmit Data
Object 21F7h (Parameter 503)
This object is required for remote control. The data
type is UNSIGNED16.
The internal parameter 503 of the easYgen must be
set to react on the remote control instructions. This is
performed by sending rising signals for the respective
bits (refer to Fig. 263 for the priority of start and stop
signals).
Unit
Bit field
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Ext. Acknowledge (rising
edge) Must be set twice
to acknowledge
Must always be set to 0
Must always be set to 0
Stop bit (rising edge)
Start bit (rising edge)
easYgen-2200/2500 | Genset Control
Data type
Note
unsigned1
6
To acknowledge, a 0 must be written
and then a 1
To stop, a 0 must be written and then
a 1
To start, a 0 must be written and then
a 1
Appendix