Additional Information; D-Sub Connector Housing; Can Bus Pin Assignments Of Third-Party Units - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Appendix
Additional Information > CAN Bus Pin Assignments Of...
LDSS dynamic
Dynamic characteristic
Dynamic power level
Constants
Low dynamic
Moderate dynamic
High dynamic
Example for moderate dynamic
9.7

Additional Information

9.7.1

D-SUB Connector Housing

9.7.2

CAN Bus Pin Assignments Of Third-Party Units

D-SUB DE9 connector
602
= [(max. generator load – min. generator load) * dynamic] + (min. generator load)
= (dynamic characteristic) * (generator rated power)
= 25 %
= 50 %
= 75 %
Dynamic characteristic = [(80 % – 40 %) * 50 %] + (40 %) =
n
60 %
Dynamic power level = (60 %) * (200 kW) = 120 kW
n
Some housings for D-Sub connectors are too wide to plug them
into the unit properly. If your serial or CAN bus cable is equipped
with a housing, which does not fit into the easYgen socket, you
may replace the housing with one of the following housings:
Manufacturer
FCT
(www.fctgroup.com)
Wuerth Electronic
(www.we-online.de)
Male / plug
Terminal
Signal
1
-
2
CAN_L
3
CAN_GND
4
-
5
(CAN_SHLD)
6
(GND)
7
CAN_H
easYgen-2200/2500 | Genset Control
Type/Order No.
FKH1 FKC1G
618009214622 260809 41800927911
Female / socket
Description
Reserved
CAN Bus Signal (dominant low)
CAN ground
Reserved
Optional shield
Optional CAN ground
CAN Bus Signal (dominant high)