Configuration
Configure Application > Configure Controller > Load Share Control
ID
Parameter
5630
React. power
load share
factor
4.5.12.7.8
Load Share Control Grouping
302
CL
Setting range
Description
[Default]
2
10 to 99 %
It is possible to change the emphasis placed on maintaining control variables.
By increasing or decreasing the percentage value in this parameter, the con‐
[50 %]
trol places a higher priority on maintaining the primary or secondary control
reference variable.
If the value for this parameter is configured higher, maintaining the primary
control variable has a higher priority. If the value for this parameter is config‐
ured lower, maintaining the secondary control variable has a higher priority.
Primary control variable
n
Secondary control variable
n
Notes
The smaller this factor the higher the priority to equally share the load among
all generators.
If 99 % is configured here, only the primary control reference variable is con‐
sidered. If 10 % is configured here, only the secondary control reference vari‐
able is considered.
Load sharing with several gensets is possible for a supply of a
maximum of four split busbars. A group breakers splits the busbar
in a way that some gensets supply one busbar and some supply
another one. However, it is necessary to group the gensets, which
supply the same busbar, into segments.
The configured segment number can be changed to one of three
alternative segment numbers. The LogicsManager is used to
implement this.
easYgen-2200/2500 | Genset Control
Isolated operation = voltage maintained
Isolated operation = reactive power sharing with other generators main‐
tained
37535B