Configuration
Configure Application > Inputs And Outputs > Analog Inputs
ID
Parameter
Offset
1046
Input 1
1096
Input 2
1146
Input 3
Sender con‐
nection type
1041
Input 1
1091
Input 2
1141
Input 3
Monitoring
wire break
212
CL
Setting range
Description
[Default]
2
-20.0 to 20.0
The resistive input (the "0 to 500 Ohm" analog input) may be calculated with a
Ohm
permanent offset to adjust for inaccuracies.
[0.0 Ohm]
If the offset feature is utilized, the value configured in this parameter will be
added to/subtracted from the measured resistive value.
This has the following effect to the measured values (please note tables in
Ä Chapter 9.1.2 "VDO Inputs Characteristics" on page 486 ):
-20.0 to 0.1
n
Ohm
n
+0.1 to 20.0
n
Ohm
n
Notes
This parameter is only visible if the parameter "Sender type"
(1020 Ä p. 211/1070 Ä p. 211/1120 Ä p.
Ohm".
2
This parameter defines the type of the used sender.
[Two wire]
A two-pole sender is connected to the easYgen. The unit measures the
sender values between the dedicated terminals.
One wire
A single-pole sender is connected to the easYgen. The unit measures the
sender values between the terminal of the analog input and the engine
ground terminal.
Notes
This parameter is only visible if the parameter "Sender type"
(1020 Ä p. 211/1070 Ä p. 211/1120 Ä p.
Ohm".
Refer to
2
The respective analog input can be monitored for wire breaks.
If this protective function is triggered, the display indicates "Wb: {Text of
Parameter [Description]}" (parameter
1025 Ä p. 210/1075 Ä p. 210/1125 Ä p.
The following configurations are used to monitor for wire breaks:
[Off]
No wire break monitoring is performed.
High
If the actual value rises over the maximum value (overshoot), this is identified
as a wire break.
Low
If the actual value falls below the minimum value (undershoot), this is identi‐
fied as a wire break.
High/Low
If the actual value rises over the maximum value (overshoot) or falls below
the minimum value (undershoot), this is identified as a wire break.
easYgen-2200/2500 | Genset Control
VDO temperature: The displayed value will decrease.
VDO pressure: The displayed value will increase.
VDO temperature: The displayed value will increase.
VDO pressure: The displayed value will decrease.
Ä Chapter 3.2.12 "Analog Inputs" on page 72 for wiring details.
211) is configured to "0 to 500
211) is configured to "0 to 500
210).