Appendix
LogicsManager Reference > Factory Settings
Simple (function)
If TRUE, the unit recognizes that the ignition
speed has been reached.
Deactivated by default.
[00.3x] Flag {y}; {x} = 0 to 5, {y} = 9 to 14
If TRUE, flag {y} becomes TRUE.
Deactivated by default
Not available in operation modes "STOP" and
"MAN".
[00.36] Flag 15
If TRUE, flag 15 becomes TRUE.
Prepared for GCB fail to close or Synchroniza‐
tion time GCB.
Not available in operating modes "STOP" and
"MAN".
[00.37] Flag 16
If TRUE, flag 16 becomes TRUE.
Prepared for Critical mode or Start without load.
Not available in operating modes "STOP" and
"MAN".
[00.81] Setpoint 2 frequency enabled
If TRUE, the frequency setpoint 2 is enabled.
Deactivated by default.
Not available in operating modes "STOP" and
"MAN".
[00.82] Setpoint 2 load enabled
582
Extended (configuration)
easYgen-2200/2500 | Genset Control
Result
FALSE
FALSE
dependent on
GCB fail to
close and
Synchroniza‐
tion time GCB
dependent on
Critical mode
and Start
without load
FALSE