37426B easYgen-2000 Series Genset Control Installation Software Version 1.xxxx Manual 37426B...
Page 2
Provides other helpful information that does not fall under the warning or caution categories. Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward is believed to be correct and reliable. However, Woodward assumes no responsibility unless otherwise expressly undertaken.
Manual 37426B easYgen-2000 Series - Genset Control Revision History Rev. Date Editor Changes NEW 09-06-09 Release 09-10-09 Minor changes 10-01-14 Minor changes Content 1. G ..................8 HAPTER ENERAL NFORMATION Document Overview ..........................2. E ............9 HAPTER LECTROSTATIC ISCHARGE WARENESS 3.
Series - Interfaces 37430 easYgen-2000 Series - Parameter List 37431 DE37431 easYgen-2000 Series - Brief Operation Informa- 37432 DE37432 tion Table 1-1: Manual - overview Intended Use The unit must only be operated in the manner described by this manual. The prerequisite for a proper and safe operation of the product is correct transportation, storage, and installation as well as careful oper- ation and maintenance.
Application ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ The easYgen-2000 Series has no internally isolated power supply. For marine applications an EMI filter (i.e. SCHAFFNER - FN 2070-3-06) must be connected ahead of the power supply input. To meet the functional safety requirements of the application, the rules of marine classification independent protec- tive devices must be applied.
Manual 37426B easYgen-2000 Series - Genset Control Chapter 4. Housing Panel Cutout ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ h' h H Figure 4-1: Housing - panel-board cutout Measure Description Tolerance Height Total 171 mm Panel cutout 138 mm + 1.0 mm Housing dimension 136 mm...
Manual 37426B easYgen-2000 Series - Genset Control Clamp Fastener Installation ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ For installation into a panel door with the fastening clamps, please proceed as follows: Panel cutout Cut out the panel according to the dimensions in Figure 4-1. Note: It is not necessary to drill the holes if the fastening clamps are used.
Manual 37426B easYgen-2000 Series - Genset Control Screw Kit Installation ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ In order to enhance the protection of the front to IP 65, it is possible to fasten the unit with a screw kit instead of the clamp fastener hardware.
Manual 37426B easYgen-2000 Series - Genset Control Chapter 5. Wiring Diagrams Service Port (RS-232) Direct Configuration Connect only with Woodward DPC cable Relay [R 1] isolated Cable Fixed to Ready for operation 480 Vac Mains | Busbar Voltage N 120 Vac...
Manual 37426B easYgen-2000 Series - Genset Control Service Port (RS-232) Direct Configuration Connect only with Woodward DPC cable Relay [R 1] isolated Cable Fixed to Ready for operation 480 Vac Mains | Busbar Voltage N 120 Vac Relay [R 2] isolated...
Manual 37426B easYgen-2000 Series - Genset Control Service Port (RS-232) Direct Configuration Connect only with Woodward DPC cable Relay [R 1] isolated Cable Fixed to Ready for operation 480 Vac Mains | Busbar Voltage N 120 Vac Relay [R 2] isolated...
Manual 37426B easYgen-2000 Series - Genset Control Relay [R 7] isolated Fixed to „Command: open GCB“ if GCB open relay used (NC, NO) otherwise preconfigured to „mains decoupling“ Relay [R 8] isolated [DI 10] Discrete input [DI 10] isolated Fixed to „Command: close MCB“...
Manual 37426B easYgen-2000 Series - Genset Control Chapter 6. Connections WARNING All technical data and ratings indicated in this chapter are not definite! Only the values indicated in Chapter 7: Technical Data on page 64 are valid! The following chart may be used to convert square millimeters [mm²] to AWG and vice versa: mm²...
Table 6-2: Power supply - terminal assignment Figure 6-2: Power supply - crank waveform at maximum load NOTE Woodward recommends to use one of the following slow-acting protective devices in the supply line to terminal 53: • Fuse NEOZED D01 6A or equivalent •...
DO NOT use both sets of voltage measuring inputs. The control unit will not measure voltage correctly if the 120 V and 480 V inputs are utilized simultaneously. NOTE Woodward recommends protecting the voltage measuring inputs with slow-acting fuses rated for 2 to 6 A. Voltage Measuring: Generator...
Manual 37426B easYgen-2000 Series - Genset Control Voltage Measuring: Generator, Parameter Setting '1Ph 2W' (1-phase, 2-wire) NOTE The 1-phase, 2-wire measurement may be performed phase-neutral or phase-phase. Please note to configure and wire the easYgen consistently. Refer to the Configuration Manual 37427 for more infor- mation.
Manual 37426B easYgen-2000 Series - Genset Control Voltage Measuring: Mains (Busbar), Parameter Setting '1Ph 2W' (1-phase, 2-wire) NOTE The 1-phase, 2-wire measurement may be performed phase-neutral or phase-phase. Please note to configure and wire the easYgen consistently. Refer to the Configuration Manual 37427 for more infor- mation.
Manual 37426B easYgen-2000 Series - Genset Control Voltage Measuring: Busbar (Mains), Parameter Setting '1Ph 2W' (1-phase, 2-wire) NOTE The 1-phase, 2-wire measurement may be performed phase-neutral or phase-phase. Please note to configure and wire the easYgen consistently. Refer to the Configuration Manual 37427 for more infor- mation.
Manual 37426B easYgen-2000 Series - Genset Control Current Measuring ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ CAUTION Before disconnecting the device, ensure that the current transformer/CT is short-circuited. Generator Current NOTE Generally, one line of the current transformers secondary is to be grounded close to the CT.
Manual 37426B easYgen-2000 Series - Genset Control Mains Current 1-Phase NOTE Generally, one line of the current transformers secondary is to be grounded close to the CT. Detail: Connection of the transducers ../{x} A {x} = 1 or 5 Mains...
Manual 37426B easYgen-2000 Series - Genset Control Ground Current The mains current input can be configured to measure the mains current or ground current. Depending on how Parameter 'Input mains current as' is configured will determine if this input will measure the mains current (de- fault) or the ground current.
Manual 37426B easYgen-2000 Series - Genset Control Power Measuring ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ If the unit's current transformers are wired according to the diagram shown, the following values are displayed. Parameter Description Sign displayed Generator real power Genset generating kW + Positive Generator real power...
Page 46
Manual 37426B easYgen-2000 Series - Genset Control Different power factor displays at the unit: i0.91 (inductive) c0.93 (capacitive) lg.91 (lagging) ld.93 (leading) Reactive power display at the unit: 70 kvar (positive) -60 kvar (negative) Output at the interface: + (positive)
Manual 37426B easYgen-2000 Series - Genset Control Discrete Inputs: Operation Logic Discrete inputs may be configured to normally open (N.O.) or normally closed (N.C.) states. In the state N.O., no potential is present during normal operation; if an alarm is issued or control operation is performed, the input is energized.
Manual 37426B easYgen-2000 Series - Genset Control Relay Outputs (LogicsManager) ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ max. 250 Vac/dc external device Relay output external device Figure 6-52: Relay outputs Terminal Description Term. Com. Form A, N.O. make contact Type Relay output [R 01] Ready for operation 2.5 mm²...
Page 52
Manual 37426B easYgen-2000 Series - Genset Control CAUTION The discrete output "Ready for operation OFF" must be wired in series with an emergency stop func- tion. This means that it must be ensured that the generator circuit breaker is opened and the engine is stopped if this discrete output is de-energized.
Manual 37426B easYgen-2000 Series - Genset Control Analog Inputs (FlexIn) ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ NOTE There is a mixed operation of resistor senders and 0/4 to 20 mA senders possible. Please consider the following application references. Wiring Resistor Senders Wiring Two-Pole Senders Analog input [AI 04]...
Manual 37426B easYgen-2000 Series - Genset Control Wiring Single-Pole Senders An accuracy of ≤ 2.5% may be achieved when using single-pole senders. The specified accuracy of 2.5% for ≤ single-pole sensors can only be achieved if the differential voltage between the genset chassis ground and PE does not exceed +/- 2.5V.
Manual 37426B easYgen-2000 Series - Genset Control Wiring Single and Two-Pole Senders Simultaneously An accuracy of ≤ 2.5% may be achieved when using single-pole senders. It is possible to combine single- and two-pole senders. The specified accuracy of 2.5% for single-pole sensors can only be achieved if the differen- ≤...
Manual 37426B easYgen-2000 Series - Genset Control Wiring 0/4 to 20 mA Senders The 0/4 to 20 mA inputs can be used for one or two pole senders. Analog input [AI 04] 0 to 500 Ohms | 0 to 20 mA...
Manual 37426B easYgen-2000 Series - Genset Control Analog Outputs ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Controller configuration and an external jumper can change the multifunction controller bias output signals. The analog outputs are galvanically isolated. Controller Wiring Speed / power controller Speed / power controller...
Manual 37426B easYgen-2000 Series - Genset Control Figure 6-58: Analog controller output 3/4 - Wiring and external jumper setting Type Terminal Description 2.5 mm² Analog output AO 03 (easYgen 2500 P1 only) 2.5 mm² Current 2.5 mm² Analog output AO 04 (easYgen 2500 P1 only) 2.5 mm²...
Service Port (RS-232) The optional Woodward Direct Configuration Cable (DPC) must be connected to the Service Port. The DPC adapter has a single RS-232 interface which is used for the configuration setup of the easYgen-2000 Series. Figure 6-60: RS-232 interface - overview...
CAN Bus Interfaces (FlexCAN) CAN Bus 1 (easYgen-2000 Series) Terminal Description CAN-L CAN-H Table 6-44: CAN bus 1 - pin assignment (easYgen-2000 Series) CAN Bus 2 (easYgen-2200 P2 only) Terminal Description CAN-L CAN-H Table 6-45: CAN bus 2 - pin assignment (easYgen-2200 P2 only)
• The configured baud rate is too high for bus length • The CAN bus cable is routed in close proximity with power cables Woodward recommends the use of shielded, twisted-pair cables for the CAN bus (i.e.: Lappkabel Unitronic LIYCY (TP) 2×2×0.25, UNITRONIC-Bus LD 2×2×0.22).
Manual 37426B easYgen-2000 Series - Genset Control “Transfer rate LS fast message” to 0,30 s. Bus Shielding The table below gives a detailed overview how the different interfaces needs to be shielded. Device Interface Shielding easYgen-2200 P1 CAN 1 External RC element...
Page 63
Manual 37426B easYgen-2000 Series - Genset Control NOTE For a continuous operation with the direct configuration cable DPC (e.g. remote control of the easY- gen), it is required to use at least revision F (P/N 5417-557 Rev. F) of the DPC. When using a DPC of an earlier revision, problems may occur in continuous operation.
Manual 37426B easYgen-2000 Series - Genset Control Chapter 7. Technical Data Nameplate ------------------------------------------------------------------------------------------------------ Serial number (numerical) Date of production (YYMM) Serial number (Barcode) Item number Item revision number Details Technical data Type Description (long) Type Description (short) Approval Approvals Measuring values, voltages ------------------------------------------------------------------------------ /∆...
Manual 37426B easYgen-2000 Series - Genset Control Interface -------------------------------------------------------------------------------------------------------- Service Port (RS-232) ..............galvanically not isolated Version ........................RS-232 Signal level ........................5V RS-485 interface ................galvanically isolated Insulation voltage (continuously) ................100 Vac Insulation test voltage ( 5s) .................. 1000 Vac ≤...
Manual 37426B easYgen-2000 Series - Genset Control Chapter 8. Environmental Data Vibration--------------------------------------------------------------------------------------------------------- Frequency Range – Sine Sweep ..............5Hz to 100Hz Acceleration ......................4G Standards ..........................EN 60255-21-1 (EN 60068-2-6, Fc) Lloyd’s Register, Vibration Test2 SAEJ1455 Chassis Data Frequency Range - Random ................. 10Hz to 500Hz Power Intensity ...................
Manual 37426B easYgen-2000 Series - Genset Control Chapter 9. Accuracy Measuring value Display Accuracy Measuring start Notes Frequency Generator 15.0 to 85.0 Hz 0.1 % (of 5 % (of PT secondary Mains 40.0 to 85.0 Hz 85 Hz) voltage setting) Voltage 1.5 % (of PT second-...
Page 69
Manual 37426B easYgen-2000 Series - Genset Control Reference conditions (for measuring the accuracy): • Input voltage ......sinusoidal rated voltage • Input current ......sinusoidal rated current • Frequency ......... rated frequency +/- 2 % • Power supply ......rated voltage +/- 2 % •...
Manual 37426B easYgen-2000 Series - Genset Control Appendix A. Useful Information Connecting 24 V Relays ≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡≡ Interferences in the interaction of all components may affect the function of electronic devices. One interference factor is disabling inductive loads, like coils of electromagnetic switching devices. When disabl- ing such a device, high switch-off induces voltages may occur, which might destroy adjacent electronic devices or result interference voltage pulses, which lead to functional faults, by capacitive coupling mechanisms.
Manual 37426B easYgen-2000 Series - Genset Control Advantages and disadvantages of different interference suppressing circuits are described in the following. Connection diagram Load current / voltage curve Advantages Disadvantages • Uncritical dimensioning • High release delay • Lowest possible induced voltage •...
Page 72
Phone +49 (0) 711 789 54-0 • Fax +49 (0) 711 789 54-100 stgt-info@woodward.com Homepage http://www.woodward.com/power Woodward has company-owned plants, subsidiaries, and branches, as well as authorized distributors and other authorized service and sales facilities throughout the world. Complete address/phone/fax/e-mail information for all locations is available on our website (www.woodward.com).