Woodward easYgen-2000 Series User Manual page 280

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Configuration
Configure Application > Configure Controller > Load Control
ID
Parameter
5527
Load setpoint
2
5521
Int. load con‐
trol setpoint 2
(Internal load
control setpoint
2)
12919
Setp. 2 load
(Setpoint 2 load)
5522
Load control
setpoint ramp
5523
Load control
setpoint max‐
imum
5524
Minimum gen.
import/export
280
CL
Setting range
Description
[Default]
06.03
Analog input 3
Analog input 3 is used to control the setpoint
Notes
Selecting a different data source may cause the controller to not operate
properly.
The load setpoint may be adjusted between 0 and the configured load control
setpoint maximum (parameter
2
Import
The value entered for the import level shall always be supplied by the utility.
All load swings are absorbed by the generator(s) provided the load rating for
the generator(s) is not exceeded. The generator will always start when an
import power operation is enabled.
Export
The value entered for the export level shall always be supplied to the utility.
All load swings are absorbed by the generator(s) provided the load rating for
the generator(s) is not exceeded. The generator will always start when an
export power operation is enabled.
[Constant]
The generator shall always supply the value entered for the constant power
level. All load swings are absorbed by the utility. The generator will always
start when a constant power (base load) operation is enabled.
0
0.0 to 9999.9
The load setpoint 2 is defined in this screen. This value is the reference for
kW
the load controller when performing parallel operations.
[200.0 kW]
2
Determined by
If this LogicsManager condition is TRUE, the frequency setpoint 2 will be ena‐
LogicsManager
bled, i.e. the setting of parameter
parameter
[(0 & 1) & 1]
Notes
For information on the LogicsManager and its default settings see
Ä Chapter 9.4.1 "LogicsManager Overview" on page 549 .
2
0.10 to 100.0 %/
The different setpoint values are supplied to the controller via this ramp. The
s
slope of the ramp is used to alter the rate at which the controller modifies the
setpoint value. The faster the change in the setpoint is to be carried out, the
[3.00 %/s]
greater the value entered here must be.
Notes
This ramp is also used in isolated operation for loading or unloading an addi‐
tional genset. An excessive oscillation may occur if the ramp is configured too
high.
2
0 to 150 %
If the maximum generator load is to be limited, a percentage based on the
rated generator power (parameter
[100 %]
controller adjusts the generator in such a manner that this value is not
exceeded. This parameter limits the setpoint of the load controller when the
generator is in a mains parallel operation.
2
0 to 100 %
If the minimum generator load is to be limited, a percentage based on the
rated generator power (parameter
[0 %]
controller will not permit the load to drop below the configured load limit value.
This parameter is only functional when the generator is in a mains parallel
operation.
easYgen-2200/2500 | Genset Control
5523 Ä p.
5540 Ä p. 279
5539 Ä p.
278.
1752 Ä p.
1752 Ä p.
280).