Woodward easYgen-2000 Series User Manual page 337

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

CAN connection troubleshooting
Fault description
Connection error (ToolKit freezes
when trying to establish a connec‐
tion)
SID files for additional CANopen
devices
37535B
Cause
Active connections
via infrared ports
Active connections
via bluetooth
Additional CANopen
devices connected to
the bus
When connecting a PC to the easYgen via CAN bus, other external
CANopen devices (like a Phoenix Contact I/O expansion board, for
example) may cause ToolKit to fail to connect.
A cause may be that ToolKit looks for a SID file for the external
device, which does not exist.
A special *.sid file can be created in this case.
For additional support feel free to contact Woodward.
Create a SID (text) file with the following content:
n
<?xml version="1.0" encoding="utf-8"?>
<ServiceInterfaceDefinition
xmlns:xsi="http://www.w3.org/
Identifier="[device application name]"
Specification="EmptyFile">
</ServiceInterfaceDefinition>
Name the file [CANopen device identifier].sid
n
Store the file in the configured SID directory
n
easYgen-2200/2500 | Genset Control
Access Via PC (ToolKit) > Connect ToolKit
Remedy
Temporarily deactivate the infrared port
(including virtual ports)
Temporarily deactivate bluetooth (including
virtual ports)
Contact Woodward support or provide
missing .sid file for additional CANopen
Ä "SID files for additional CANopen
device (
devices" on page 337 )
2001/XMLSchema-instance"
Operation
337

Advertisement