Woodward easYgen-2000 Series User Manual page 238

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Configuration
Configure Application > Engine > Engine Start/Stop
Auxiliary operations
Fig. 92: : Engine - auxiliary services timing
ID
Parameter
3302
Start attempts
4102
Start attempts
critical mode
3306
Starter time
(Maximum
starter delay
[tST])
238
The auxiliary operations start, as soon as the engine is to be
started or a running engine is detected.
At the same time, the discrete output for the auxiliary services
(LogicsManager 03.01) will be enabled. This discrete output
remains enabled as long as speed is detected or if the controller is
in the MANUAL mode.
CL
Setting range
Description
[Default]
2
1 to 20
The control will attempt to start the engine with this number of start attempts.
[3]
If the engine fails to start after the configured number of attempts, an alarm
will be initiated.
An engine has been successfully started if the ignition speed reaches the
configured firing speed and the delayed engine monitoring has expired.
2
1 to 20
If a critical operation mode (
on page 244 ) is initiated, the engine will continue to attempt to start for the
[10]
number of starts configured here.
An engine has been successfully started if the ignition speed reaches the
configured firing speed and the delayed engine monitoring has expired.
2
1 to 99 s
This is the maximum time that the starter relay will remain energized ("Start"
display).
[5 s]
If the LogicsManager output "Ignition speed reached" = TRUE, the speed/fre‐
quency have reached firing speed, or the time has expired, the relay will be
de-energized.
easYgen-2200/2500 | Genset Control
Ä Chapter 4.5.10 "Emergency Run"
37535B