Interface - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Technical Specifications
Technical Data > Interface
Auxiliary excitation (D+) input/
output
Magnetic pickup input
8.1.4

Interface

Service Port interface
RS-485 interface
CAN bus interface
476
Auxiliary excitation (D+) input/output
Output current
Voltage monitoring range (input)
Monitoring accuracy
Magnetic pickup input
Input impedance
Input voltage
Fig. 251: MPU - characteristic
Service Port interface
Proprietary interface
RS-485 interface
Insulation voltage (continuously)
Insulation test voltage (≤ 5 s)
Version
Operation
CAN bus interface
Insulation voltage (continuously)
Insulation test voltage (≤ 5 s)
easYgen-2200/2500 | Genset Control
Not isolated
50 mA@12 Vdc
100 mA@24 Vdc
8 to 40.0 Vdc
≤ 1 %
Capacitively isolated
min. approx. 17 kΩ
Refer to Fig. 251
Not isolated
Connect only with Woodward
DPC cable
Isolated
100 Vac
1000 Vac
RS-485 Standard
Half-duplex
Isolated
100 Vac
1000 Vac
37535B