3.2.5

Voltage Measuring

General notes
3.2.5.1

Generator Voltage

General notes
Schematic and terminals
37535B
Setup Connections > Voltage Measuring > Generator Voltage
Terminal
Description
A
53
Battery B+ (8 to 40.0 Vdc)
B
52
Auxiliary excitation (D+) output
Table 3: Charging alternator - terminal assignment
NOTICE!
Incorrect readings due to improper setup
The control unit will not measure voltage correctly if
the 120 V and 480 V inputs are utilized simultaneously.
Never use both sets of voltage measuring inputs.
Woodward recommends protecting the voltage meas‐
uring inputs with slow-acting fuses rated for 2 to 6 A.
If parameter
rated volt.") is configured with a value between 50 and
130 V, the 120 V input terminals must be used for
proper measurement.
If parameter
rated volt.") is configured with a value between 131
and 480 V, the 480 V input terminals must be used for
proper measurement.
Fig. 24: Voltage measuring - generator - wiring
easYgen-2200/2500 | Genset Control
1800 Ä p. 99
("Gen. PT secondary
1800 Ä p. 99
("Gen. PT secondary
Installation
A
max
2.5 mm²
2.5 mm²
43