6.4.9

Wiring Self Powered Discrete Inputs

6.4.10

Setup Phoenix Expansion Modules

Supported Phoenix modules
Bus coupler
IL CAN BK
Possible combinations
37535B
Special Applications > Setup Phoenix Expansion Mo...
In order to create self-powered discrete inputs:
1.
Connect battery negative (B-) to ground and function earth
(terminal 55).
Fig. 184: Wiring self-powered discrete inputs
2.
Connect DI common (terminal 43) to power supply 12/24 V
(terminal 53, minimum wire size 0.5 mm² (20 AWG)).
ð This enables to energize the discrete inputs against
ground.
Discrete outputs
IB IL 24 DO 2
IB IL 24 DO 8
IB IL 24 DO 16
Phoenix module ILB CO 24 DI 16 DO 16 is not sup‐
ported.
The possible combinations of Phoenix modules are listed below.
The parameters display the maximum extension.
It is also possible to connect fewer modules.
easYgen-2200/2500 | Genset Control
Application
Discrete inputs
IB IL 24 DI 2
IB IL 24 DI 4
IB IL 24 DI 8
IB IL 24 DI 16
397