Advertisement

Configuration
Configure Application > Configure Controller > Voltage Control
ID
Parameter
5618
Voltage set‐
point 1 source
5600
Int.voltage
control set‐
point 1
5619
Voltage set‐
point 2 source
288
CL
Setting range
Description
[Default]
2
Determined by
The voltage setpoint 1 source may be selected from the available data
AnalogManager
sources.
Even it is possible to select all data sources
on page 533 ), only the following data sources may be used:
[05.07]
Internal voltage setpoint 1
Internal voltage control setpoint 1 (parameter
point 1
05.08
Internal voltage setpoint 2
Internal voltage control setpoint 2 (parameter
point 1
05.09
Interface voltage setpoint
The setpoint, which is transmitted via the interface, is used as setpoint
05.15
Discrete raise/lower voltage
The setpoint from the discrete raise/lower voltage function is used as setpoint
06.01
Analog input 1
Analog input 1 is used to control the setpoint
06.02
Analog input 2
Analog input 2 is used to control the setpoint
06.03
Analog input 3
Analog input 3 is used to control the setpoint
06.04
Analog input 4
Analog input 4 is used to control the setpoint
Notes
Selecting a different data source may not allow the controller to operate prop‐
erly.
The voltage setpoint may be adjusted within the configured operating limits
Ä Chapter 4.4.1.1 " Generator Operating Voltage / Frequency" on page 107 ).
(
0
50 to 650,000 V
The internal generator voltage setpoint 1 is defined in this screen. This value
is the reference for the voltage controller when performing isolated and/or no-
[400 V]
load operations.
2
Determined by
The voltage setpoint 2 source may be selected from the available data
AnalogManager
sources.
Even it is possible to select all data sources
on page 533 ), only the following data sources may be used:
05.07
Internal voltage setpoint 1
Internal voltage control setpoint 1 (parameter
point 2
[05.08]
Internal voltage setpoint 2
Internal voltage control setpoint 2 (parameter
point 2
05.09
Interface voltage setpoint
The setpoint, which is transmitted via the interface, is used as setpoint
easYgen-2200/2500 | Genset Control
Ä Chapter 9.3.1 "Data Sources"
5600 Ä p.
288) is used as set‐
5601 Ä p.
289) is used as set‐
Ä Chapter 9.3.1 "Data Sources"
5600 Ä p.
288) is used as set‐
5601 Ä p.
289) is used as set‐
37535B