Generator Reverse/Reduced Power (Level 1 & 2) Ansi# 32R/F - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

ID
Parameter
2201
Alarm class
2207
2213
2202
Self acknowl‐
edge
2208
2214
4.4.1.7
Generator Reverse/Reduced Power (Level 1 & 2) ANSI# 32R/F
General notes
Configuration examples
37535B
Configure Monitoring > Generator > Generator Reverse/Reduced ...
CL
Setting range
Description
[Default]
2
Class A/B/C/D/
Each limit may be assigned an independent alarm class that specifies what
E/F
action should be taken when the limit is surpassed.
2201: [E]
2207: [F]
2213: [F]
Notes
For additional information refer to
on page 587
2
Yes
The control unit automatically clears the alarm if the fault condition is no
longer detected.
[No]
The control unit does not automatically reset the alarm when the fault condi‐
tion is no longer detected.
The alarm must be acknowledged and reset by manually pressing the appro‐
priate buttons or by activating the LogicsManager output "External acknowl‐
edgement" (via a discrete input or via an interface).
The power produced by the generator is calculated from the
voltage and current values measured in accordance with how
parameters "Generator voltage measuring" (param‐
eter
1851 Ä p.
1850 Ä p.
The generator power limits may be configured for reduced power
and/or reverse power depending on the threshold values entered.
The note below explains how a reduced or reverse power limit is
configured.
If the single-phase or three-phase measured real power is below
the configured limit of the reduced load or below the configured
value of the reverse power, an alarm will be issued.
Refer to
for the triggering characteristic of this monitoring function.
The values for reverse /reduced power monitoring can be config‐
ured as follows:
easYgen-2200/2500 | Genset Control
Ä Chapter 9.5.1 "Alarm Classes"
96) and "Generator current measuring" (parameter
97) are configured.
If this protective function is triggered, the display indi‐
cates "Gen. rev./red. pwr.1" or "Gen. rev./red. pwr.2"
and the logical command variable "06.12" or "06.13"
will be enabled.
Ä Chapter 9.1.1 "Triggering Characteristics" on page 481
Definition
Reduced power Fault initiated if the monitored real
power falls below the configured (positive) limit.
Reverse power Fault initiated if the direction of the
monitored real power reverses and the configured
(negative) limit is exceeded.
Configuration
115