Generator Rated Active Power

Analog output example
Flexible limit example
9.3.2.5

Generator Rated Reactive Power

37535B
Analog Manager Reference > Reference Values > Generator Rated Reactive P...
The rated system frequency (parameter
n
configured to 50 Hz.
The source value at maximum output is configured to 110.00
n
% (of the rated frequency i.e. 55 Hz).
The source value at minimum output is configured to 90.00
n
% (of the rated frequency i.e. 45 Hz).
The analog output range is configured to 0 to 20 mA.
n
If a frequency of 45 Hz (or below) is measured, the analog
n
output issues its lower limit (i.e. 0 mA).
If a frequency of 55 Hz (or above) is measured, the analog
n
output issues its upper limit (i.e. 20 mA).
If a frequency of 50 Hz is measured, the analog output
n
issues 50 % of its upper limit (i.e. 10 mA).
If a frequency of 51 Hz is measured, the analog output
n
issues 60 % of its upper limit (i.e. 12 mA).
The rated system frequency (parameter
n
configured to 50 Hz.
If the flexible limit is to be configured to 105.00 % (of the
n
rated frequency i.e. 52.5 Hz), it must be entered as 10500.
All generator active power values refer to the generator rated
active power (parameter
The generator rated active power (parameter
n
is configured to 500 kW.
The source value at maximum output is configured to 120.00
n
% (of the rated active power i.e. 600 kW).
The source value at minimum output is configured to 0.00 %
n
(of the rated active power i.e. 0 kW).
The analog output range is configured to 0 to 20 mA.
n
If an active power of 0 kW is measured, the analog output
n
issues its lower limit (i.e. 0 mA).
If an active power of 600 kW (or above) is measured, the
n
analog output issues its upper limit (i.e. 20 mA).
If an active power of 300 kW is measured, the analog output
n
issues 50 % of its upper limit (i.e. 10 mA).
If an active power of 120 kW is measured, the analog output
n
issues 20 % of its upper limit (i.e. 4 mA).
The generator rated active power (parameter
n
is configured to 500 kW.
If the flexible limit is to be configured to 120.00 % (of the
n
rated active power i.e. 600 kW), it must be entered as
12000.
All generator reactive power values refer to the generator rated
reactive power (parameter
easYgen-2200/2500 | Genset Control
1750 Ä p.
1750 Ä p.
1752 Ä p.
95).
1758 Ä p.
95).
Appendix
94) is
94) is
1752 Ä p.
95)
1752 Ä p.
95)
541

Advertisement

Table of Contents
loading

Table of Contents