LogicsManager Reference > Logical Command Variables
Name
Function
External DO 4
If this logical output becomes true, the external relay output 4 will be activated
External DO 5
If this logical output becomes true, the external relay output 5 will be activated
External DO 6
If this logical output becomes true, the external relay output 6 will be activated
External DO 7
If this logical output becomes true, the external relay output 7 will be activated
External DO 8
If this logical output becomes true, the external relay output 8 will be activated
External DO 9
If this logical output becomes true, the external relay output 9 will be activated
External DO 10
If this logical output becomes true, the external relay output 10 will be activated
External DO 11
If this logical output becomes true, the external relay output 11 will be activated
External DO 12
If this logical output becomes true, the external relay output 12 will be activated
External DO 13
If this logical output becomes true, the external relay output 13 will be activated
External DO 14
If this logical output becomes true, the external relay output 14 will be activated
External DO 15
If this logical output becomes true, the external relay output 15 will be activated
External DO 16
If this logical output becomes true, the external relay output 16 will be activated
Relay
Number
Term.
Internal relay outputs
[R1]
30/31
[R2]
32/33
[R3]
34/35
[R4]
36/37
[R5]
38/39/40
[R6]
41/42
[R7]
80/81
[R8]
82/83
[R9]
84/85
[R10]
86/87
[R11]
88/89
9.4.4

Logical Command Variables

556
Application mode (parameter
None
GCBopen
LogicsManager; pre-assigned with 'Ready for operation OFF'
CAUTION! Only relay [R 01] has an inverse logic. The relay opens (all other relays
close), if the logical output of the LogicsManager becomes TRUE.
LogicsManager; pre-assigned with 'Centralized alarm (horn)'
LogicsManager; pre-assigned with 'Starter'
LogicsManager; pre-assigned with 'Diesel: Fuel solenoid, Gas: Gas valve'
LogicsManager; pre-assigned with 'Warning alarm'
LogicsManager
LogicsManager
Command: open GCB
LogicsManager; pre-assigned with 'Mains decoupling'
LogicsManager; pre-assigned with 'Stop solenoid'
LogicsManager; pre-assigned with 'Auxiliary services'
LogicsManager; pre-assigned with 'Shut down alarm'
The logical command variables are grouped into different catego‐
ries
Group 00: Flags condition 1
n
Group 01: Alarm system
n
easYgen-2200/2500 | Genset Control
3401 Ä p.
200)
GCB
Command: close GCB
Number
00.66
00.67
00.68
00.69
00.70
00.71
00.72
00.73
00.74
00.75
00.76
00.77
00.78
GCB/MCB
Command: open
MCB
Command: close
MCB
37535B