6.4.4.1

Operating Modes

AUTOMATIC
Fig. 151: LogicsManager function
"Operat. mode AUTO"
37535B
Special Applications > Performing Remote Start/St... > Operating Modes
Refer to Ä Chapter 5.2.2 "Basic Navigation"
on page 341 for a detailed description of the navigation
through the various display screens.
A detailed description of the individual parameters may
be found in Ä Chapter 4.5.11 "Automatic Run"
on page 246.
Be sure to enter the password for code level 2 or
higher to be able to access the required configuration
screens.
Refer to Ä Chapter 5.1.1 "Install ToolKit" on page 331
for a description of the installation, configuration and
usage of the ToolKit visualization and configuration
application.
Preliminary Conditions
We recommend to reset the unit to factory settings
before proceeding.
Refer to Ä Chapter 4.1.5 "System Management"
on page 92 for reference.
The LogicsManager factory settings are shown in
Ä Chapter 9.4.5 "Factory Settings" on page 578.
Two operating modes may be used with remote control:
AUTOMATIC
n
STOP
n
It is possible to fix the operating mode using the LogicsManager
function 00.16 "Operat. mode AUTO" (parameter
The LogicsManager function "Operat. mode AUTO" (param‐
eter
12510 Ä p.
(Fig. 151).
ð AUTOMATIC operation mode is always enabled.
If an alarm of alarm class C through F occurs in AUTOMATIC
operating mode, the control does not return to STOP operating
mode. If the alarm is cleared after acknowledgement a restart is
initiated.
It is also possible to configure a discrete input for controlling the
operating mode using the LogicsManager function 00.16 "Operat.
mode AUTO" (parameter
mode STOP" (parameter
easYgen-2200/2500 | Genset Control
247) can be configured as shown in
12510 Ä p.
247) and 00.18 "Operat.
12530 Ä p.
248).
Application
12510 Ä p.
247).
377