Generator Time-Overcurrent (Level 1, 2 & 3) Ansi# 50/51 - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Configuration
Configure Monitoring > Generator > Generator Time-Overcurrent...
ID
Parameter
2053
Delayed by
engine speed
2059
4.4.1.6
Generator Time-Overcurrent (Level 1, 2 & 3) ANSI# 50/51
General notes
ID
Parameter
2200
Monitoring
2206
2212
2204
Limit
2210
2216
2205
Delay
2211
2217
114
CL
Setting range
Description
[Default]
2
[Yes]
Monitoring for fault conditions is not performed until engine delayed moni‐
toring is enabled. The engine monitoring delay time (param‐
eter
parameters assigned this delay.
No
Monitoring for this fault condition is continuously enabled regardless of engine
speed.
Current is monitored according to how the parameter "Generator
current measuring" (parameter
controller provides the user with three definite time alarm levels for
generator overcurrent faults.
Monitoring of the maximum phase current is performed in three
steps. Every step can be provided with a delay time independent of
the other steps.
Refer to
for the triggering characteristic of this monitoring function.
CL
Setting range
Description
[Default]
2
[On]
Overcurrent monitoring is carried out according to the following parameters.
Monitoring is performed at three levels. All three values may be configured
independent from each other (prerequisite: Level 1 < Level 2 < Level 3).
Off
Monitoring is disabled for Level 1 limit, Level 2 limit, and/or Level 3 limit.
2
50.0 to 300.0 %
The percentage values that are to be monitored for each threshold limit are
defined here.
2204: [110.0 %]
If this value is reached or exceeded for at least the delay time without inter‐
2210: [150.0 %]
ruption, the action specified by the alarm class is initiated.
2216: [250.0 %]
Notes
This value refers to the System rated frequency (parameter
2
0.02 to 99.99 s
If the monitored generator current exceeds the threshold value for the delay
time configured here, an alarm will be issued.
2205: [30.00 s]
2211: [1.00 s]
2217: [0.40 s]
Notes
If the monitored generator voltage falls below the threshold (minus the hyste‐
resis) before the delay expires the time will be reset.
easYgen-2200/2500 | Genset Control
3315 Ä p.
239) must expire prior to fault monitoring being enabled for
1850 Ä p.
If this protective function is triggered, the display indi‐
cates "Gen. overcurrent 1", "Gen. overcurrent 2", or
"Gen. overcurrent 3" and the logical command variable
"06.09", "06.10.", or "06.11" will be enabled.
Ä Chapter 9.1.1 "Triggering Characteristics" on page 481
97) is configured. This
1754 Ä p.
95).