Woodward easYgen-2000 Series User Manual page 531

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Remote frequency setpoint
Remote voltage setpoint
External DI request (1 to 16)
Bit 15
Bit 14
Bit 13
Bit 12
Bit 11
Bit 10
Bit 9
Bit 8
Bit 7
Bit 6
Bit 5
37535B
Data Protocols > Additional Data Identifier > Transmit Data
External discrete input 16 [DIex16]
External discrete input 15 [DIex15]
External discrete input 14 [DIex14]
External discrete input 13 [DIex13]
External discrete input 12 [DIex12]
External discrete input 11 [DIex11]
External discrete input 10 [DIex10]
External discrete input 9 [DIex09]
External discrete input 8 [DIex08]
External discrete input 7 [DIex07]
External discrete input 6 [DIex06]
easYgen-2200/2500 | Genset Control
Object 21FDh (Parameter 509)
This value may be used as data source "[05.03] Inter‐
face freq. setp." via the Analog Manager. No password
is required to write this value.
This object is required to transmit the frequency set‐
point for frequency control.
The data type is INTEGER16.
The valid range for this value is [Hz * 100].
Example
50.00 Hz = 5000 = 1388h
Object 21FEh (Parameter 510)
This value may be used as data source "[05.09] Inter‐
face volt.setp." via the Analog Manager. No password
is required to write this value.
This object is required to transmit the voltage setpoint
for voltage control.
The data type is UNSIGNED32.
The value is scaled in [V].
Example
400 V = 400 = 190h
10000 V = 10000 = 2710h
Object 3F4Dh (Parameter 8014)
This object is required to receive the state of the
external discrete inputs 1 to 16 (e.g. of a Phoenix
expansion card). The data type is UNSIGNED16.
Appendix
531