Woodward easYgen-2000 Series User Manual page 73

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Wiring two-pole senders
37535B
VDO, 0 to 180 Ohm; 0 to 5 bar, Index "III"; 0 to 10 bar, Index
n
"IV"
VDO, 0 to 380 Ohm; 40 to 120°, Index "92-027-004; 50 to 125°,
n
Index "92-027-006
A catalog of all available VDO sensors is available for
download at the VDO homepage (http://www.vdo.com)
Mixed operation of resistor senders and 0 to 20 mA
senders is possible. Please consider the following
application references.
Fig. 58: Analog inputs - wiring two-pole senders
Terminal
Description
54
Power supply 0 Vdc
53
Power supply 12/24 Vdc (8 to 40.0 Vdc)
10
Analog input [AI 01/02/03] ground, connected to 0 Vdc
11
Analog input [AI 01]
12
Analog input [AI 02]
13
Analog input [AI 03]
Table 27: Wiring two-pole senders
Terminal
Description
67
Analog input [AI 04] ground, connected to 0 Vdc
68
Analog input [AI 04]
Table 28: Wiring two-pole senders (easYgen-2500 P1 only)
easYgen-2200/2500 | Genset Control
Installation
Setup Connections > Analog Inputs
A
max
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
A
max
2.5 mm²
2.5 mm²
73

Advertisement

Table of Contents
loading

Table of Contents