Multi-Unit Parameter Alignment - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

ID
Parameter
3500
Monitoring
3506
3504
Limit
3510
3505
Delay
3511
3501
Alarm class
3507
3502
Self acknowl‐
edge
3508
3503
Delayed by
engine speed
3509
4.4.6.10

Multi-Unit Parameter Alignment

General notes
37535B
Configure Monitoring > Miscellaneous > Multi-Unit Parameter Alig...
CL
Setting range
Description
[Default]
2
[On]
Undervoltage monitoring of the battery voltage is carried out according to the
following parameters. Both values may be configured independent from each
other (prerequisite: Level 1 > Level 2).
Off
Monitoring is disabled for Level 1 limit and/or Level 2 limit.
2
8.0 to 42.0 V
The threshold values that are to be monitored are defined here.
3404: [24.0 V]
If the monitored battery voltage reaches or falls below this value for at least
the delay time without interruption, the action specified by the alarm class is
3510: [20.0 V]
initiated.
Notes
The default monitoring limit for battery undervoltage is 24 Vdc after 60 sec‐
onds.
This is because in normal operation the terminal voltage is approximately
26 Vdc (alternator charged battery).
2
0.02 to 99.99 s
If the battery voltage falls below the threshold value for the delay time config‐
ured here, an alarm will be issued.
3405: [60.00 s]
3511: [10.00 s]
Notes
If the battery voltage exceeds the threshold (plus the hysteresis) again before
the delay expires the time will be reset.
2
Class A/B/C/D/
Each limit may be assigned an independent alarm class that specifies what
E/F/Control
action should be taken when the limit is surpassed.
[B]
Notes
For additional information refer to
on page 587
2
Yes
The control unit automatically clears the alarm if the fault condition is no
longer detected.
[No]
The control unit does not automatically reset the alarm when the fault condi‐
tion is no longer detected.
The alarm must be acknowledged and reset by manually pressing the appro‐
priate buttons or by activating the LogicsManager output "External acknowl‐
edgement" (via a discrete input or via an interface).
2
Yes
Monitoring for fault conditions is not performed until engine delayed moni‐
toring is enabled. The engine monitoring delay time (param‐
eter
parameters assigned this delay.
[No]
Monitoring for this fault condition is continuously enabled regardless of engine
speed.
The multi-unit parameter alignment functionality requires that the
relevant parameters are all configured identically at all participating
units.
easYgen-2200/2500 | Genset Control
Ä Chapter 9.5.1 "Alarm Classes"
3315 Ä p.
239) must expire prior to fault monitoring being enabled for
Configuration
187

Advertisement

Table of Contents
loading

Table of Contents