Woodward easYgen-2000 Series User Manual page 522

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Appendix
Data Protocols > CANopen > Protocol 6000 (Load Share...
Load share bus communication
Load share bus communication - "fast" refreshed data
Mux
Byte
Bit
F
0
1
2
3
4
5
0
1
2
3
4
5
6
7
6
0-4
5
6
7
7
Load share bus communication - "normal" refreshed data
Mux
Byte
Bit
N0
0
1
2
3
4
5
0-3
522
Function
3
Generator real load capacity utilization rate, L-Byte
Generator real load capacity utilization rate, H-Byte
Generator reactive load capacity utilization rate, L-
Byte
Generator reactive load capacity utilization rate, H-
Byte
Active power load sharing is enabled
Reactive power load sharing is enabled
GCB is closed
MCB is closed
GGB (generator group breaker) is closed
Dead bus closure request is active
Mains settling time is running
Shutdown alarm is active (alarm class C,D,E,F)
Bus segment / node
Not used
LDSS: add-on request enabled
LDSS: add-off request enabled (reserved)
Not used
Function
1
Generator real load, L-Byte, L-Word
Generator real load, H-Byte, L-Word
Generator real load, L-Byte, H-Word
Generator real load, H-Byte, H-Word
Real load control state
easYgen-2200/2500 | Genset Control
Remark
Mux identifier
Integer [‰], unsigned
Integer [‰], unsigned
Dead bus detection
Back synchronization to mains
Max. 32 nodes possible
Load dependent start / stop
Load dependent start / stop
Remark
Mux identifier
Long [W]
2: Static
3: Isochronous
4: Base load control
5: Export/import control
10:Load share
0, 1, 6, 7, 8, 9, 11, ... : internal
37535B