Woodward easYgen-2000 Series User Manual page 384

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Application
Special Applications > Connecting An IKD 1 On CAN...
ID
Parameter
9300
COB-ID
9121
Event timer
8970
Selected Data
Protocol
Table 73: RPDO1 configuration
Fig. 161: RPDO configuration for IKD
1 (example HMI)
Fig. 162: RPDO configuration for IKD
1 (example ToolKit)
384
Configure RPDO1 as shown below.
Value
Comment
201 (hex) / 513
The COB-ID is configured to 201 (hex) or 513 (dec)
(dec)
2000 ms
The event timer is configured to 2000 ms
65000
Data protocol 65000 is selected
ð (Fig. 161) and (Fig. 162) display the example RPDO con‐
figuration for IKD 1.