Woodward easYgen-2000 Series User Manual page 75

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

Wiring 0 to 20 mA senders (single-
or two-pole)
37535B
Fig. 60: Analog inputs - wiring single- and two-pole senders
Terminal
Description
54
Power supply 0 Vdc
53
Power supply 12/24 Vdc (8 to 40.0 Vdc)
10
Analog input [AI 01/02/03] ground
11
Analog input [AI 01]
12
Analog input [AI 02]
13
Analog input [AI 03]
Table 31: Wiring single and two-pole senders simultaneously
Terminal
Description
67
Analog input [AI 04] ground, connected to 0 Vdc (terminal
54)
68
Analog input [AI 04]
Table 32: Wiring single and two-pole senders simultaneously
(easYgen-2500 P1 only)
The 0 to 20 mA inputs can be used for one or two pole senders.
easYgen-2200/2500 | Genset Control
Installation
Setup Connections > Analog Inputs
A
max
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
2.5 mm²
A
max
2.5 mm²
2.5 mm²
75

Advertisement

Table of Contents
loading

Table of Contents