Password System; Configure Measurement - Woodward easYgen-2000 Series User Manual

Genset control
Hide thumbs Also See for easYgen-2000 Series:
Table of Contents

Advertisement

ID
Parameter
4.1.6

Password System

General notes
ID
Parameter
10415
Basic code
level
10413
Commis‐
sioning code
level
10414
Commis‐
sioning code
level
10412
Temp. super‐
comm. level
code
10411
Supercommis‐
sioning level
code
4.2

Configure Measurement

General notes
37535B
CL
Setting range
Description
[Default]
[No]
The event history will not be cleared.
Notes
This parameter is only displayed, if Factory Settings (parameter
1703 Ä p.
CL
Setting range
Description
[Default]
1
0 to 9999
The password for the code level "Service" is defined in this parameter.
[-]
Refer to
3
0 to 9999
The password for the code level "Commission" is defined in this parameter.
[-]
Refer to
3
0 to 9999
The algorithm for calculating the password for the code level "Temporary
Commissioning" is defined in this parameter.
[-]
5
0 to 9999
The algorithm for calculating the password for the code level "Temporary
Supercommissioning" is defined in this parameter.
[-]
5
0 to 9999
The password for the code level "Supercommissioning" is defined in this
parameter.
[-]
Refer to
easYgen-2200/2500 | Genset Control
92) is set to "Yes".
The following passwords grant varying levels of access
to the parameters.
Each individual password can be used to access the
appropriate configuration level through multiple access
methods and communication protocols (via the front
panel, via serial RS-232/485 interface, and via the
CAN bus).
Ä Chapter 4.1.4 "Enter Password" on page 89 for default values.
Ä Chapter 4.1.4 "Enter Password" on page 89 for default values.
Ä Chapter 4.1.4 "Enter Password" on page 89 for default values.
If the easYgen is intended to be operated in parallel
with the mains, the mains voltage measuring inputs
must be connected.
Configuration
Configure Measurement
93